| 2014-02-26 18:41:39 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR |
| | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS |
| | AND ARE TO INCLUDE ALL INFORMATION FOR THE ENGINEER |
| | REQUIRED BY FAC61G15-23.002. IT IS NOT CLEAR WHICH OF |
| | THE VARIOUS COMPANY NAMES AND ADDRESSES ON THE PLAN ARE |
| | FOR THE ENGINEER. NO CERTIFICATE OF AUTHORIZATION |
| | NUMBER PROVIDED, AND THE ADDRESSES ON THE PLAN DO NOT |
| | MATCH DBPR RECORDS FOR THIS ENGINEER. PLEASE INCLUDE. |
| | |
| | 2. FBC 107: |
| | |
| | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| | SECTION 107.3.5). |
| | |
| | MANY SHEETS ARE NOT SIGNED AND SEALED AND ARE MARKED |
| | "INFORMATIONAL." SOME SHEETS HAVE FASTENING |
| | SPECIFICATIONS, SO THIS IS A DESIGN, NOT |
| | "INFORMATIONAL". PLEASE HAVE THE STRUCTURAL ENGINEER |
| | SIGN AND SEAL ANY SHEETS WITH STRUCTURAL |
| | SPECIFICATIONS. FOR EXAMPLE, A11, ITEM 5. |
| | |
| | 3. FASTENING SPECIFICATIONS FOR ALL COMPONENTS REQUIRED |
| | TO BE COMPLETE - NUMBER OF FASTENERS, TYPE OF FASTENER, |
| | DIAMETER, MINIMUM EMBEDMENT IF APPLICABLE. FBC 1609. |
| | |
| | 4. WIND DESIGN CRITERIA REQUIRED TO BE ON THE PLAN, FBC |
| | 1603.1.4. |
| | |
| | 5. SOME SHEETS ARE NOT LEGIBLE; FOR INSTANCE, DETAIL 6 |
| | ON SHEET A4. PRIOR TO RESUBMITTAL, CONFIRM THAT ALL |
| | INFORMATION ON THE PLANS ARE LEGIBLE. IF THE |
| | INFORMATION IS NOT REQUIRED, REMOVE FROM THE PLAN, FBC |
| | 107. |
| | |
| | 6. CABINETS ARE SHOWN AS PROPOSED. PROVIDE DCA APPROVAL |
| | OR ENGINEERING FOR CABINETS, FBC 1609. |
| | |
| | |