| Plan Review Notes For Permit 14020268 |
| Permit Number |
14020268 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-04-01 14:07:51 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. ONE SET OF PLANS WAS SUBMITTED FOR TWO SEPARATE | | | PERMITS, 14020268 (ADD CURBING & STRIPING) AND 14020269 | | | (RELOCATE SITE LIGHTING). SOME COMMENTS APPEAR TO BE | | | ADDRESSED FROM 14020269 BUT NOT ALL. FOR INSTANCE, | | | STRUCTURAL DETAIL REQUIRED WAS NOT SUBMITTED. | | | | | | 2. AS PLANS NEED TO BE REVISED, PLEASE INCORPORATE | | | ACCESSIBILITY INFORMATION INTO THE PLAN. INITIALLY IT | | | WAS AGREED THAT A LETTER COULD BE SUBMITTED, BUT ONLY | | | ONE WAS SUBMITTED (TWO REQUIRED FOR PERMIT ISSUANCE) | | | AND I WAS UNAWARE THAT PLAN SHEETS HAD TO CHANGE TO | | | ADDRESS OTHER REVIEWER'S COMMENTS ON THE OTHER PERMIT | | | (14020269). PLANS WILL NEED TO BE CHANGED AGAIN AS THE | | | STRUCTURAL DETAIL REQUIRED WAS NOT SUBMITTED. | | | | | | 3. PLEASE SEE COMMENTS ON BOTH PERMITS. REVISE PLANS TO | | | ADDRESS ALL COMMENTS, ALL TRADES, AND RESUBMIT. | | | | | | |
|