| Plan Review Notes For Permit 14020232 |
| Permit Number |
14020232 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-02-26 17:53:58 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. PLANS ARE NOT CLEAR AS TO SCOPE AND LOCATION OF | | | PROPOSED IMPROVEMENT. THE PLAN PROVIDED DOES NOT | | | INDICATE WHAT IS EXISTING AND WHAT IS PROPOSED, FBC | | | 107. APPLICATION STATES THAT A TRENCH WILL BE CUT AND | | | POURED BACK. IT APPEARS THAT MORE WORK THAN THAT WILL | | | BE DONE. STRUCTURAL DETAIL FOR TRENCH INFILL NOT | | | PROVIDED. | | | | | | 2. IT IS NOT CLEAR HOW THE STRUCTURE WILL BE AFFECTED | | | BY PROPOSED IMPROVEMENT. SEE FBC 107.2.1: | | | | | | ALL INFORMATION, DRAWINGS,SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | | SECTION 107.3.5). | | | | | | CALCULATIONS OR PLANS PREPARED BY A DESIGN PROFESSIONAL | | | MAY BE REQUIRED. | | | | | | 3. VALUE IS TO INCLUDE LABOR, MATERIALS, PROFIT, | | | OVERHEAD. PROVIDE A COST BREAKDOWN FOR PROPOSED WORK | | | INCLUDING INSTALLED EQUIPMENT. | | | |
|