| 2014-11-06 12:58:20 | | | | 14020230 | | | 6651 N. JOG ROAD | | | ELEVATOR PLAN | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | PROVIDE AN ELECTRICAL RISER PLAN SHOWING THE FEEDERS | | | AND DISCONNECTS FOR THE ELEVATORS. INCLUDE EMERGENCY | | | FEEDERS AND TRANSFER SWITCHES. NEC 215.5, 620.3, | | | 620.13, 620.14, 620.51 | | | | | | INDICATE THE LOCATION OF THE ELEVATOR PANELBOARD. SHOW | | | ALL WORKING CLEARANCES. NEC 215.5, 620.5 | | | | | | RECEPTACLES IN ELEVATOR EQUIPMENT ROOMS AND PITS | | | REQUIRE GFCI PROTECTION. NEC 620.23, 620.85 | | | | | | A SEPARATE BRANCH CIRCUIT SHALL SUPPLY ELEVATOR CAR | | | LIGHTS. NEC 620.22 | | | | | | ROBERT LECKY, CBO | | | ELECTRICAL PLANS REVIEW | | | 561-373-3701 | | | [email protected] | | | |
|