| Date |
Text |
| 2014-02-20 16:14:43 | 6651 NORTH JOG ROAD - ELEVATORS |
| | TRACKING #14020230 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | PER NFPA 101 SECTION 9.4.3 ALL NEW ELEVATORS SHALL |
| | CONFORM TO THE FIRE FIGHTERS' EMERGENCY OPERATIONS |
| | REQUIREMENTS OF ASME A17.1/CSA B44, SAFETY CODE FOR |
| | ELEVATORS AND ESCALATORS. |
| | |
| | PROVIDE A DETAIL SHOWING THE ELEVATOR CONTROL BUTTONS, |
| | KEY SWITCH OVER-RIDES, ETC. |
| | |
| | PROVIDE A DRAWING NOTE INDICATING THE FOLLOWING: PER |
| | NFPA 101 SECTION 9.4.6.2 ALL ELEVATORS EQUIPPED WITH |
| | FIRE FIGHTERS' EMERGENCY OPERATIONS SHALL BE SUBJECT TO |
| | A MONTHLY OPERATION WITH A WRITTEN RECORD OF THE |
| | FINDINGS MADE AND KEPT ON THE PREMISES AS REQUIRED BY |
| | ASME A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND |
| | ESCALATORS. |
| | |
| | PER NFPA 101 SECTION 9.4.5 ELEVATOR MACHINE ROOMS. |
| | ELEVATOR MACHINE ROOMS THAT CONTAIN SOLID-STATE |
| | EQUIPMENT FOR ELEVATORS, OTHER THAN EXISTING ELEVATORS, |
| | HAVING A TRAVEL DISTANCE EXCEEDING 50 FEET ABOVE THE |
| | LEVEL OF EXIT DISCHARGE, OR EXCEEDING 30 FEET BELOW THE |
| | LEVEL OF EXIT DISCHARGE, SHALL BE PROVIDED WITH |
| | INDEPENDENT VENTILATION OR AIR-CONDITIONING SYSTEMS TO |
| | MAINTAIN TEMPERATURE DURING FIRE FIGHTERS' EMERGENCY |
| | OPERATIONS FOR ELEVATOR OPERATION. THE OPERATING |
| | TEMPERATURE SHALL BE ESTABLISHED BY THE ELEVATOR |
| | EQUIPMENT MANUFACTURER'S SPECIFICATIONS. WHEN STANDBY |
| | POWER IS CONNECTED TO THE ELEVATOR, THE MACHINE ROOM |
| | VENTILATION OR AIR-CONDITIONING SHALL BE CONNECTED TO |
| | STANDBY POWER. |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | FIRE INVESTIGATOR & INSPECTOR |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| | |
| | |
| | |
| | |
| | |
| | |