| | BUILDING PLAN REVIEW |
| | REVISION: 14020230 |
| | PERMIT: 12040748 |
| | ADD: 6651 N JOG |
| | CONT: KBR |
| | TEL: (561 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. FEB.26/2014 |
| | ACTION: DENIED |
| | |
| | 1) SHEET 200-A3-102 PLEASE PROVIDE RATING OF BOTH |
| | ELEVATOR SHAFT AND STAIRWELL, PROVIDE WALL DETAILS. |
| | 708.4 FIRE-RESISTANCE RATING. |
| | SHAFT ENCLOSURES SHALL HAVE A FIRE-RESISTANCE RATING OF |
| | NOT LESS THAN 2 HOURS WHERE CONNECTING FOUR STORIES OR |
| | MORE, AND NOT LESS THAN 1 HOUR WHERE CONNECTING LESS |
| | THAN FOUR STORIES. THE NUMBER OF STORIES CONNECTED BY |
| | THE SHAFT ENCLOSURE SHALL INCLUDE ANY BASEMENTS BUT NOT |
| | ANY MEZZANINES. SHAFT ENCLOSURES SHALL HAVE A |
| | FIRE-RESISTANCE RATING NOT LESS THAN THE FLOOR ASSEMBLY |
| | PENETRATED, BUT NEED NOT EXCEED 2 HOURS. SHAFT |
| | ENCLOSURES SHALL MEET THE REQUIREMENTS OF SECTION |
| | 703.2.1. |
| | |
| | 2) THE PLANS DO NOT PROVIDE WHERE THE LOCATION OF THE |
| | ELEVATOR MACHINE ROOM IS LOCATED, PLEASE PROVIDE |
| | COMPLIANCE WITH: |
| | 3006.4 MACHINE ROOMS AND MACHINERY SPACES. |
| | ELEVATOR MACHINE ROOMS AND MACHINERY SPACES SHALL BE |
| | ENCLOSED WITH FIRE BARRIERS CONSTRUCTED IN ACCORDANCE |
| | WITH SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED |
| | IN ACCORDANCE WITH SECTION 712, OR BOTH. THE |
| | FIRE-RESISTANCE RATING SHALL NOT BE LESS THAN THE |
| | REQUIRED RATING OF THE HOISTWAY ENCLOSURE SERVED BY THE |
| | MACHINERY. OPENINGS IN THE FIRE BARRIERS SHALL BE |
| | PROTECTED WITH ASSEMBLIES HAVING A FIRE PROTECTION |
| | RATING NOT LESS THAN THAT REQUIRED FOR THE HOISTWAY |
| | ENCLOSURE DOORS. |
| | |
| | 3) PLEASE SHOW COMPLIANCE WITH: |
| | 3004.2 LOCATION OF VENTS. |
| | VENTS SHALL BE LOCATED AT THE TOP THE HOISTWAY AND |
| | SHALL OPEN EITHER DIRECTLY TO THE OUTER AIR OR THROUGH |
| | NONCOMBUSTIBLE DUCTS TO THE OUTER AIR. NONCOMBUSTIBLE |
| | DUCTS SHALL BE PERMITTED TO PASS THROUGH THE ELEVATOR |
| | MACHINE ROOM, PROVIDED THAT PORTIONS OF THE DUCTS |
| | LOCATED OUTSIDE THE HOISTWAY OR MACHINE ROOM ARE |
| | ENCLOSED BY CONSTRUCTION HAVING NOT LESS THAN THE |
| | FIRE-RESISTANCE RATING REQUIRED FOR THE HOISTWAY. HOLES |
| | IN THE MACHINE ROOM FLOORS FOR THE PASSAGE OF ROPES, |
| | CABLES OR OTHER MOVING ELEVATOR EQUIPMENT SHALL BE |
| | LIMITED AS NOT TO PROVIDE GREATER THAN 2 INCHES (51 MM) |
| | OF CLEARANCE ON ALL SIDES. |
| | |
| | 4) PLEASE SHOW COMPLIANCE WITH: |
| | 3004.3 AREA OF VENTS. |
| | EXCEPT AS PROVIDED FOR IN SECTION 3004.3.1, THE AREA OF |
| | THE VENTS SHALL NOT BE LESS THAN 31/2 PERCENT OF THE |
| | AREA OF THE HOISTWAY NOR LESS THAN 3 SQUARE FEET (0.28 |
| | M2) FOR EACH ELEVATOR CAR, AND NOT LESS THAN 31/2 |
| | PERCENT NOR LESS THAN 0.5 SQUARE FEET (0.047 M2) FOR |
| | EACH DUMBWAITER CAR IN THE HOISTWAY, WHICHEVER IS |
| | GREATER. OF THE TOTAL REQUIRED VENT AREA, NOT LESS THAN |
| | ONE-THIRD SHALL BE PERMANENTLY OPEN. CLOSED PORTIONS OF |
| | THE REQUIRED VENT AREA SHALL CONSIST OF OPENINGS GLAZED |
| | WITH ANNEALED GLASS NOT GREATER THAN 1/8 INCH (3.2 MM) |
| | IN THICKNESS. |
| | |
| | EXCEPTION: THE TOTAL REQUIRED VENT AREA SHALL NOT BE |
| | REQUIRED TO BE PERMANENTLY OPEN WHERE ALL THE VENT |
| | OPENINGS AUTOMATICALLY OPEN UPON DETECTION OF SMOKE IN |
| | THE ELEVATOR LOBBIES OR HOISTWAY, UPON POWER FAILURE |
| | AND UPON ACTIVATION OF A MANUAL OVERRIDE CONTROL. THE |
| | MANUAL OVERRIDE CONTROL SHALL BE CAPABLE OF OPENING AND |
| | CLOSING THE VENTS AND SHALL BE LOCATED IN AN APPROVED |
| | LOCATION. |
| | |
| | 5) SHEET 0588 1-200-LS1.1: |
| | 5A) GRIDLINES 7.87/9.04 & F.02/F.26 WHAT ID IS AREA |
| | THAT EXITS INTO THE STAIR ENCLOSURE. |
| | |
| | 5B) GRIDLINE G/H & 7.87/9.04 WHAT ARE THE ROUND OBJECTS |
| | IN THE EGRESS PATH |
| | |
| | 5C) GRIDLINE F.75/6 & 18/19 BIG BOX WHAT IS THIS THAT |
| | YOU ARE EGRESSING FROM IT DOES NOT INDICATE |
| | |
| | JAMES A. WITMER CBO |