2014-02-12 14:32:56 
 FUEL GAS/PLUMBING PLAN REVIEW
 PERMIT: 14020208
 ADD: 110 FLAGLER PROMENADE N.
 CONT: ASSURANCE POWER SYSTEMS
 TEL: (561)886-0470
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. FEB. 12/ 2014
 ACTION: DENIED
  
 GAS PERMIT APPLICATION REQUIREMENTS
  
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2010 FUEL GAS.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. FUEL GAS
 402.3.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35)
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4)
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2010 FUEL GAS CODE SEC. 304
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. 503.4.2 SPECIAL GAS VENTS. SPECIAL GAS VENTS SHALL
 BE LISTED AND INSTALLED IN ACCORDANCE WITH THE SPECIAL
 GAS VENT MANUFACTURER?S INSTALLATION INSTRUCTIONS.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2010 FUEL GAS SEC. 402.2
  
  
 COMMENT #:
 1) THE LENGTHS OF PIPE OR SECTIONS OF PIPE IN THE
 ISOMETRIC DOES NOT MATCH THAT OF THE SURVEY, IN THE
 SURVEY THE METER TO THE NEW TANKLESS WATER HEATER IS
 APPROXIMATELY 20-22 FEET WHEREAS THE ISOMETRIC SHOWS
 5'-0" OF 3/4 INCH GAL.
  
 2) THE ISOMETRIC SHOWS THE USE OF GALVANIZED PIPE AND
 TRAC PIPE (CSST) THE GAS CHARTS SUBMITTED WERE FOR SCH
 METALLIC PIPE, OMEGA FLEX TRAC PIPE & DRISCOPLEX PIPE
 (PE PLASTIC) PIPE. THE ISOMEETRIC SHOWS THE PIPE TO THE
 COOKTOP AS 3/4 INCH GALV. / TRAC TOTAL OF 40 FEET
 PROVIDE THE BREAK OUT OF TYPE OF PIPE AND LENGHT FOR
 EACH. WHERE IS THE PE PLASTIC TO BE RUN?
  
 3) PLANS DO NOT INDICATE THE TYPE OF GAS ASSUMED SINCE
 CHARTS PROVIDED ARE FOR NATURAL GAS.
  
 4) TABLES RECONIZED BY THE 2010 FBC-FUEL GAS CODE ARE
 FBC-2010 FUEL GAS SECS. 401.8 THRU 402.6.1 AND TABLES
 402.4(1) THRU 402.4(35). EACH PAGE SPECIFIES TYPE OF
 GAS, MATRIAL OF THE PIPE, INLET PRESSURE PRESSURE DROP
 AND SPECIFIC GRAVITY TO ASSURE THE CORRECT SIZING OF
 EACH PIPE SECTION.
  
 5) THE SUBMITTED MANUFACTURERS CUT SHEET IS NOT CHECK
 OFF OR CIRCLED AS TO WHICH UNIT IS TO BE INSTALLED,
 INDOOR USE ONLY (NRC111-DV) OR NRC111-SV (INDOOR/
 OUTDOOR USE)
 SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE FBC-2010
 FUEL GAS CODE SEC. 304/ SUBMIT A DETAIL SHOWING THE
 TYPE, LOCATION, SIZE AND TERMINATION OF THE GAS VENTS
 PER FBC-2010 FUEL GAS CODE SEC. 502 THRU 505.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676