| 2014-03-18 11:49:54 | 14020206 | | | 4047 OKEECHOBEE BLVD. SUITE 116 | | | INTERIOR ALTERATION | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | PROVIDE A DEDICATED SAFE WORKING SPACE FOR THE | | | RELOCATED ELECTRICAL PANEL BOARD. NEC 110.26 | | | PROVIDE A SUMMARY ELECTRICAL LOAD CALCULATION. INCLUDE | | | AN ELECTRICAL RISER PLAN SHOW EXISTING SERVICE, | | | RELOCATED FEEDERS WITH CONDUIT AND OVERCURRENT | | | PROTECTION. PROVIDE A SUMMARY PANEL SCHEDULE SHOWING | | | NEW AND EXISTING LOADS. NEC 220.12; 220.14; 220.12; | | | TABLE 220.12; 230.31 | | | | | | VERIFY THE EXISTING OCCUPANCY INCLUDES SHOW WINDOW | | | LIGHTING AND A SIGN CIRCUIT. NEC 210.62; 600.5 | | | | | | NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR ALARM | | | SYSTEMS, SECURITY AND DATA SYSTEMS. | | | | | | ROBERT LECKY, CBO | | | ELECTRICAL PLANS REVIEW | | | 561-373-3701 | | | |
|