Plan Review Notes
Plan Review Notes For Permit 14020206
Permit Number 14020206
Review Stop E
Sequence Number 1
Notes
Date Text
2014-03-18 11:49:5414020206
 4047 OKEECHOBEE BLVD. SUITE 116
 INTERIOR ALTERATION
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE A DEDICATED SAFE WORKING SPACE FOR THE
 RELOCATED ELECTRICAL PANEL BOARD. NEC 110.26
 PROVIDE A SUMMARY ELECTRICAL LOAD CALCULATION. INCLUDE
 AN ELECTRICAL RISER PLAN SHOW EXISTING SERVICE,
 RELOCATED FEEDERS WITH CONDUIT AND OVERCURRENT
 PROTECTION. PROVIDE A SUMMARY PANEL SCHEDULE SHOWING
 NEW AND EXISTING LOADS. NEC 220.12; 220.14; 220.12;
 TABLE 220.12; 230.31
  
 VERIFY THE EXISTING OCCUPANCY INCLUDES SHOW WINDOW
 LIGHTING AND A SIGN CIRCUIT. NEC 210.62; 600.5
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR ALARM
 SYSTEMS, SECURITY AND DATA SYSTEMS.
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW