| 2014-03-31 14:39:40 | NOTE: | | | PLAN SUBMITTED DOES NOT SHOW STORM WATER DRAINAGE | | | ELEMENTS. PLEASE BE ADVISED, THE CITY'S NPDES MS4 | | | PERMIT AUTHORIZES THE CITY TO DISCHARGE STORMWATERS OF | | | THE STATE IN ACCORDANCE WITH THE STORMWATER MANAGEMENT | | | PROGRAMS (SWMP). THE SWMP INCLUDES POLLUTION PREVENTION | | | MEASURES, TREATMENT OR REMOVAL TECHNIQUES AND OTHER | | | APPROPRIATE MEANS TO CONTROL THE QUALITY OF STORMWATER | | | DISCHARGED FROM THE MS4. ONE COMPONENT OF THE SWMP IS | | | TO REDUCE THE DISCHARGE OF POLLUTANTS IN STORMWATER | | | REDEVELOPED AREAS CONSISTENT WITH THE SFWMF ERP | | | REQUIREMENTS. | | | PER SFWMD CRITERIA, ALL PROJECTS SHALL PROVIDE ONSITE | | | RETENTION FOR A VOLUME EQUIVALENT TO THE FIRST INCH OF | | | RUNOFF FROM THE DEVELOPED PROJECT, OR THE TOTAL RUNOFF | | | OF 2.5 INCHES TIMES THE PERCENTAGE OF IMPERVIOUSNESS, | | | WHICHEVER IS THE GREATER. WATER SURFACE AND ROOFED | | | AREAS CAN BE DEDUCTED FROM SITE AREAS ONLY FOR | | | WATER-QUALITY PERVIOUS/IMPERVIOUS CALCULATIONS. | | | | | | MANUEL JULIAN GONZALEZ | | | ENGINEERING PROJECT COORDINATOR | | | ENGINEERING SERVICES AND PUBLIC WORKS DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | | | | | | | | | | | | | |
|