2014-02-04 17:25:432010 FBC
  
 DENIED BY BUILDING
  
 1) THE ENHANCED FASTENING CALCULATIONS FOR THE FLAT
 ROOF ARE IN ERROR. THE FASTENER SPACING CALCULATION FOR
 THE CORNER AREAS IS SPECIFIED AS 3.661237 INCHES WHICH
 IS LESS THAN THE MINIMUM SPACING OF 4" O.C. ALLOWED BY
 RAS 117. HOWEVER, INSTEAD OF ADDING ANOTHER ROW TO
 INCREASE THE FASTENER SPACING, THE ENGINEER ROUNDED UP
 AND SPECIFIED NAILING AT 4" O.C. WHICH IS NOT ALLOWED.
 PLEASE REVISE.
  