| 2014-02-05 19:00:57 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) SPECIFY THE SIZE OF EACH OF THE (2) NEW SLIDING |
| | GLASS DOORS, THE SIZE AND NUMBER OF PANELS IN EACH |
| | DOOR. CITY AMENDMENTS 107.2.1 AND FBCR 301.2.1 |
| | |
| | 2) SPECIFY THE SIZE OF EACH OF THE (3) NEW WINDOWS, THE |
| | OPENING SIZE AND CONFIGURATION. (ARE THEY ALL THE SAME |
| | SIZE? ARE ALL THREE OF THE WINDOWS INSTALLED SIDE BY |
| | SIDE IN THE SAME OPENING WITH A VERTICAL MULLION ON |
| | EACH SIDE OF THE CENTER WINDOW?) THIS IS REQUIRED IN |
| | ORDER TO DETERMINE THE SIZE OF THE MULLIONS. CITY |
| | AMENDMENTS 107.2.1 AND FBCR 301.2.1 |
| | |
| | 3) THE DRAWING SPECIFIES FIXED WINDOWS AND THE PRODUCT |
| | APPROVALS THAT WERE SUBMITTED ARE FOR SINGLE HUNG |
| | WINDOWS. PLEASE CLARIFY. CITY AMENDMENTS 107.2.1 |
| | |
| | 4) INDICATE THE TYPE OF ROOM THAT THE NEW WINDOWS WILL |
| | BE INSTALLED IN. IF IT IS A BEDROOM OR OTHER ROOM THAT |
| | WILL BE USED FOR SLEEPING SHOW THAT IT WILL COMPLY WITH |
| | FBCR 3 10.1 FOR EMERGENCY ESCAPE AND RESCUE OPENING |
| | REQUIREMENTS. |
| | |
| | 5) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE |
| | SLIDING GLASS DOORS AND THE WINDOWS ARE NOT IMPACT |
| | RATED. SHOW COMPLIANCE WITH FBCR 301.2.1.2 FOR LARGE |
| | MISSILE IMPACT PROTECTION. THE FBC EXISTING BUILDING |
| | SECTION 606.4 REQUIRES OPENING PROTECTION FOR THE NEW |
| | WINDOWS AND SLIDING GLASS DOORS, UNLESS THE AGGREGATE |
| | AREA OF THE GLAZING IN THE REPLACED COMPONENTS DOES NOT |
| | EXCEED 25 PERCENT OF THE AGGREGATE AREA OF THE GLAZED |
| | OPENINGS IN THE DWELLING. |
| | |