Plan Review Notes
Plan Review Notes For Permit 14020075
Permit Number 14020075
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2014-05-16 16:58:49THIS PLAN WAS REVIEWED BY PETER LEDUC, FIRE MARSHAL,
 WITH THE FOLLOWING COMMENTS.
  
 THE SUBMITTED PLAN, IN CONJUNCTION WITH THE ATTACHED
 LETTERS OULINING THE 1ST FLOOR OCCUPANCY, DOES NOT MEET
 THE REQUIREMENTS OF NFPA 101, LIFE SAFETY CODE, FLORIDA
 2010 EDITION, CHAPTER 17 EXISTING DAY-CARE OCCUPANCIES.
  
 MISSING REQUIREMENTS INCLUDE, BUT ARE NOT LIMITED TO, A
 LIFE SAFETY PLAN, OCCUPANY LOADS, DESK, CRIBS AND/OR
 SEATING DRAWINGS, PANIC HARDWARE, EIXT AND EMERGENCY
 LIGHTING, FIRE ALARM SYSTEM, CORRIDOR AND DOOR RATINGS,
 AND WINDOWS FOR RESCUE COMPLIANCE.
  
 ALL THESE ITEMS NEED TO BE ADDRESSED AND INDICATED ON
 FUTURE SUBMITTED PLANS.