| 2014-05-20 11:47:26 | THE PREVIOUSLY SUBMITTED PLANS WERE REVIEWED FOR |
| | ELECTRICAL COMPLIANCE ON 3/18/14 BY AN ELECTRICAL PLANS |
| | EXAMINER AND THE DEFICIENCIES WERE CLEARLY NOTED. |
| | THE RE-SUBMITTAL FAILED TO ADDRESS THE NOTES AS STATED |
| | AND THEREFORE HAVE AGAIN FAILED THE ELECTRICAL REVIEW. |
| | FROM THE PREVIOUS COMMENTS, THE ONLY ITEM ADDRESSED IS |
| | THE LOCATION OF THE ELECTRICAL PANEL, BUT YOU ARE TO |
| | PROVIDE DETAIL ON EVERY ITEMS PREVIOUSLY NOTED. |
| | 1. THE ELECTRICAL LIGHTING PLAN SHALL COMPLY WITH THE |
| | REQUIREMENTS OF FBC-ENERGY CONSERVATION SECTION 505 |
| | WHICH DICTATES MINIMUM LIGHTING CONTROLS FOR THE BOTH |
| | INTERIOR (VARIOUS ROOMS) AND EXTERIOR. AS PART OF THIS |
| | LIGHTING PLANS YOU SHALL INCLUDE THE REQUIRED EXIT AND |
| | EMERGENCY LIGHTING AS REQUIRED IN FBC 1011 |
| | 2. THE PANEL SCHEDULE REQUIRED SHALL IDENTIFY THE |
| | CIRCUITS FOR DRINKING FOUNTAINS AND EVERY OTHER |
| | REQUIRED GFCI PROTECTED CIRCUIT AS WELL. THERE SHALL BE |
| | A DEDICATED CIRCUIT WITH SPECIFIC REQUIREMENTS FOR THE |
| | REQUIRED FIRE ALARM SYSTEM. IF THE FIRE ALARM IS |
| | POWERED FROM ANOTHER PANEL STATE WHERE THE POWER SOURCE |
| | FOR THE FIRE ALARM IS. |
| | 3. YOU SHALL PROVIDE AN ELECTRICAL RISER DIAGRAM TO |
| | SHOW THE SOURCE OF POWER TO THE PANEL IN THE LOCATION |
| | AS WELL AS THE LOCATION OF THE FIRE ALARM POWER SOURCE. |
| | 4. THOUGH A SEPARATE FIRE ALARMS SHOP DRAWING AND |
| | PERMIT ARE REQUIRED, THE LOCATION OF THE FIRE ALARM |
| | DEVICES SHALL BE INCLUDED ON THE ELECTRICAL FLOOR PLAN |
| | 5. ALL RECEPTACLES SHALL BE TAMPER-RESISTANT AS PER NEC |
| | 406.11 |
| | |
| | THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL |
| | PLANS EXAMINER |
| | YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE |
| | FOLLOWING LINK: |
| | |
| | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT |
| | US.ASPX |
| | |
| | ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS |
| | EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER, |
| | AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB |
| | ABOVE THE SECOND PERMIT INFORMATION). |
| | AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR |
| | COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER |
| | PERMIT CONDITIONS. |
| | FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME. |