2014-03-05 12:18:20THE PERMIT PLAN WAS REVIEWED AND DENIED WITH THE
 FOLLOWING COMMENTS BY PETER LEDUC, FIRE MARSHAL, BUREAU
 OF FIRE PREVENTION, WEST PALM BEACH FIRE RESCUE.
  
 1. THE SUBMITTED PLANS WERE INCOMPLETE AND UNREADABLE.
  
 2. THE AREA OF OCCUPANCY CHANGE SHALL BE SOLELY
 IDENTIFIED WITH DETAILED INFORMATION SOLELY FOR THAT
 BUILDING AND OCCUPANCY.
  
 3. THE CHANGE OF OCCUPANCY SHALL MEET ALL THE
 REQUIREMENTS OF THE NFPA 101, LIFE SAFETYCODE, FLORIDA
 2010 EDITION, FOR NEW DAY-CARE OCCUPANCIES.
  
 4. EACH LIFE SAFETY REQUIRERMENT OF THAT CODE SHALL BE
 INDICATED AND ADDRESSED ON THE RE-SUBMITTED PLAN.