2014-03-18 10:42:2614020075
 1300 S. OLIVE AVENUE
 CHURCH DAY CARE
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE AN ELECTRICAL AND LIGHTING PLAN. INCLUDE AN
 ELECTRICAL PANEL SCHEDULE SHOWING ALL FEEDERS WITH OVER
 CURRENT PROTECTION AND BRANCH CIRCUITS FOR THE NEW
 OCCUPANCY. NEC 215.5
  
 SHOW LOCATION OF PANEL BOARDS. PROVIDE A DEDICATED SAFE
 WORKING SPACE FOR THE ELECTRICAL PANEL BOARDS. NEC
 110.26
  
 SHOW THE EXIT AND EMERGENCY LIGHTING WITH BATTERY BACK
 UP. FBC 1011
  
 ALL RECEPTACLES LOCATED WITHIN SIX FEET OF A SINKS AND
 WITHIN BATHROOMS AND OUTDOORS MUST BE GFCI PROTECTED.
 NEC 210.8
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC ENERGY CONSERVATION 505.3
  
 ELECTRIC DRINKING FOUNTAINS MUST BE GFCI PROTECTED. NEC
 422.52
  
 ALL RECEPTACLES SHALL BE TAMPER RESISTANT. NEC 406.12
  
 A FIRE DETECTION AND ALARM SYSTEM IS REQUIRED. FBC
 436.7
  
 A SEPARATE CIRCUIT IS REQUIRED FOR THE FIRE ALARM
 SYSTEM. NEC 760.41
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR ALARM
 SYSTEMS, SECURITY AND DATA SYSTEMS.
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW