| 2014-03-18 10:42:26 | 14020075 | | | 1300 S. OLIVE AVENUE | | | CHURCH DAY CARE | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | PROVIDE AN ELECTRICAL AND LIGHTING PLAN. INCLUDE AN | | | ELECTRICAL PANEL SCHEDULE SHOWING ALL FEEDERS WITH OVER | | | CURRENT PROTECTION AND BRANCH CIRCUITS FOR THE NEW | | | OCCUPANCY. NEC 215.5 | | | | | | SHOW LOCATION OF PANEL BOARDS. PROVIDE A DEDICATED SAFE | | | WORKING SPACE FOR THE ELECTRICAL PANEL BOARDS. NEC | | | 110.26 | | | | | | SHOW THE EXIT AND EMERGENCY LIGHTING WITH BATTERY BACK | | | UP. FBC 1011 | | | | | | ALL RECEPTACLES LOCATED WITHIN SIX FEET OF A SINKS AND | | | WITHIN BATHROOMS AND OUTDOORS MUST BE GFCI PROTECTED. | | | NEC 210.8 | | | | | | PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING | | | COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE | | | REQUIREMENTS. FBC ENERGY CONSERVATION 505.3 | | | | | | ELECTRIC DRINKING FOUNTAINS MUST BE GFCI PROTECTED. NEC | | | 422.52 | | | | | | ALL RECEPTACLES SHALL BE TAMPER RESISTANT. NEC 406.12 | | | | | | A FIRE DETECTION AND ALARM SYSTEM IS REQUIRED. FBC | | | 436.7 | | | | | | A SEPARATE CIRCUIT IS REQUIRED FOR THE FIRE ALARM | | | SYSTEM. NEC 760.41 | | | | | | NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR ALARM | | | SYSTEMS, SECURITY AND DATA SYSTEMS. | | | | | | ROBERT LECKY, CBO | | | ELECTRICAL PLANS REVIEW | | | 561-373-3701 | | | | | | |
|