Plan Review Notes
Plan Review Notes For Permit 14020075
Permit Number 14020075
Review Stop B
Sequence Number 1
Notes
Date Text
2014-02-28 16:10:44BUILDING PLAN REVIEW
 PERMIT: 14020075
 ADD: 1300 S OLIVE NO TENANT SUITE NUMBER HAS BEEN
 PROVIDED.
 CONT: TO BE DETERMINED
 TEL: (561) 644-9141 ANDREW WILSON
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. FEB. 28/ 2014
 ACTION: DENIED
  
 THE APPLICANT SUBMITTED CITY RECORDS OF THE BUILDING AT
 1300 S OLIVE A CHURCH AND SUNDAY SCHOOL WING. THESE
 DRAWINGS WILL HELP A DESIGNER OF RECORD IN DEVELOPING
 PLANS FOR A CHANGE OF OCCUPANCY FROM A A-3 PLACE OF
 WORSHIP OCCUPANCY TO DAY CARE AND MIXED USE BUILDING,
 NON-SPRINKLERED BUILDING.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION SECTION
 107.1 THE CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY
 CHAPTER 471, FLORIDA STATUTES& 61G15 FLORIDA
 ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES&
 61G1 FLORIDA ADMINISTRATIVE CODE.
  
 1) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS:
 107.3.5.1 COMMERCIAL BUILDINGS: 107.3.5.1.1 BUILDING
 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503). MIXED OCCUPANCY
 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS, OCCUPANCY SEPERTAION WALLS,
 TENANT SEPERATION, FIRE RATED CORRIDORS & HORIZONTAL
 SEPERATION 707.3.9 FLOORS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
 FIRE DAMPERS
 FIRE BLOCKING AND DRAFTSTOPPING AND CALCULATED FIRE
 RESISTANCE
 5.LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL
 INCLUDE THE FOLLOWING
 REQUIREMENTS:
 OCCUPANT LOAD AND EGRESS CAPACITIES
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 EMERGENCY LIGHTING AND EXIT SIGNS
 6.SPECIFIC OCCUPANCY REQUIREMENTS DAYCARE SEE FBC-B
 SECTION 436, 1029.4.1 DAYCARE EGRESS WINDOWS
 7.ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE
 FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 VERTICAL ACCESSIBILITY
 TOILET AND BATHING FACILITIES
 DRINKING FOUNTAINS
 EQUIPMENT
 SPECIAL OCCUPANCY REQUIREMENTS
 8. INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT)
 LIGHT AND VENTILATION
 SANITATION
  
 2) THIS IS A CHANGE OF USE, OCCUPANCY AND THE 2010
 FBC-EXISTING BUILDING CODE WOULD BE USED TO DESIGN THE
 NEW OCCUPANCY. THE DESIGNER OF RECORD WILL NEEDPROVIDE
 WHICH COMPLIANCE METHOD THE PLANS WERE DEVELOPED:
 101.5 COMPLIANCE METHODS.
 THE REPAIR, ALTERATION, CHANGE OF OCCUPANCY, ADDITION
 OR RELOCATION OF ALL EXISTING BUILDINGS SHALL COMPLY
 WITH ONE OF THE METHODS LISTED IN SECTIONS 101.5.1
 THROUGH 101.5.3 AS SELECTED BY THE APPLICANT.
 APPLICATION OF A METHOD SHALL BE THE SOLE BASIS FOR
 ASSESSING THE COMPLIANCE OF WORK PERFORMED UNDER A
 SINGLE PERMIT UNLESS OTHERWISE APPROVED BY THE CODE
 OFFICIAL. SECTIONS 101.5.1 THROUGH 101.5.3 SHALL NOT BE
 APPLIED IN COMBINATION WITH EACH OTHER. FOR THE
 REMAINDER OF THIS REVIEW THE REVIEW WILL BE COMPLETED
 UNDRE THE WORK AREA METHOD.
  
 3) 901.3 CHANGE OF OCCUPANCY CLASSIFICATION.
 WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING
 CHANGES, THE PROVISIONS OF SECTIONS 902 THROUGH 912
 SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY
 CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF
 OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT
 GROUP
 PLEASE REVIEW ALL CODE SECTIONS. IF THE CODE REFERANCES
 SECTION 902THROUGH 912, THIS IS ALL THE SECTIONS UNDER
 THE EXISTING BUILDING CODE.
 THE CODE WILL ALSO REFERANCE THE FLORIDA BUILDING CODE-
 BUILDING AS WELL AS THE FLORIDA FIRE PREVENTION CODE.
  
 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]