| Plan Review Notes For Permit 14020067 |
| Permit Number |
14020067 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-02-11 08:44:06 | BY RL | | | | | | 14020067 | | | 112 N. DIXIE HWY. | | | 7-ELEVEN | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING | | | COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE | | | REQUIREMENTS. FBC ENERGY CONSERVATION 505.3 | | | | | | SHOW THE LOCATION OF THE ELECTRICAL SERVICE WITH | | | DISCONNECT ON A SITE PLAN WITH PROPERTY LINES. VERIFY | | | THE ELECTRICAL SERVICE MAINS SERVING THIS BUILDING ARE | | | SIX OR LESS AND GROUPED IN ONE LOCATION. SHOW ALL | | | METERS, GROUNDING, MAIN DISCONNECTS AND PANEL BOARDS | | | FOR THE BUILDING SERVICE INCLUDING ALL OTHER EXISTING | | | OCCUPANCIES REQUIRING ELECTRICAL SERVICE. | | | NEC 230.2, 230.71, 230.72 | | | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION | | | FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING | | | MEANS. NEC 110.22, 110.16, 110.22 | | | | | | NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR ALARM | | | SYSTEMS, SECURITY AND DATA SYSTEMS. | | | | | | ROBERT LECKY, CBO | | | ELECTRICAL PLANS REVIEW | | | 561-373-3701 | | | |
|