| 2014-02-04 13:42:50 | PLUMBING PLAN REVIEW |
| | PERMIT: 13121076/ ISOLATED FOOTINGS & FOUNDATION |
| | ADD: 8151 OKEECHOBEE BLVD |
| | CONT: P & T CONSTRUCTION |
| | TEL: (561)324-8055 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | ARCHITECT: TERCILLA COURTEMANCHE 561-478-4457 |
| | RENE TERCILLA |
| | |
| | PLUMBING ENGINEER: RGD CONSULTING ENGINEERS |
| | 561-743-0165 |
| | MICHAEL J. BISHOP |
| | |
| | 1ST REVIEW |
| | DATE: TUESDAY FEB. 04/2014 |
| | ACTION: BUILDING PROVISO |
| | |
| | 1) 2010 CHAPTER 1 ADMINISTRATIVE CODE 105.13. |
| | SPECIAL PHASED PERIMETER & ISOLATED FOUNDATION PERMIT |
| | APPROVAL- NO SLAB WORK |
| | |
| | AFTER SUBMITTAL OF THE APPROPRIATE CONSTRUCTION |
| | DOCUMENTS, THE BUILDING OFFICIAL IS AUTHORIZED TO ISSUE |
| | A PERMIT FOR THE CONSTRUCTION OF FOUNDATIONS OR ANY |
| | OTHER PART OF A BUILDING OR STRUCTURE BEFORE THE |
| | CONSTRUCTION DOCUMENTS FOR THE WHOLE BUILDING OR |
| | STRUCTURE HAVE BEEN SUBMITTED. THE HOLDER OF SUCH |
| | PERMIT FOR THE FOUNDATION OR OTHER PARTS OF A BUILDING |
| | OR STRUCTURE SHALL PROCEED AT THE HOLDER'S OWN RISK |
| | WITH THE BUILDING OPERATION AND WITHOUT ASSURANCE THAT |
| | A PERMIT FOR THE ENTIRE STRUCTURE WILL BE GRANTED. |
| | CORRECTIONS MAY BE REQUIRED TO MEET THE REQUIREMENTS OF |
| | THE TECHNICAL CODES. THIS PROVISION IS ONLY FOR THE |
| | FLORIDA BUILDING CODE, ALL OTHER AGENCY APPROVALS |
| | NECESSARY FOR CONSTRUCTION MUST BE SECURED PRIOR TO |
| | THIS PROVISION BEING APPLIED. |
| | |
| | 2) 2010 FBC-PLUMBING 305.4 SLEEVES. |
| | ANNULAR SPACES BETWEEN SLEEVES AND PIPES SHALL BE |
| | FILLED OR TIGHTLY CAULKED IN AN APPROVED MANNER. |
| | ANNULAR SPACES BETWEEN SLEEVES AND PIPES IN |
| | FIRE-RESISTANCE-RATED ASSEMBLIES SHALL BE FILLED OR |
| | TIGHTLY CAULKED IN ACCORDANCE WITH THE FLORIDA BUILDING |
| | CODE, BUILDING. |
| | |
| | 2010 FBC-PLUMBING 305.5 PIPES THROUGH OR UNDER FOOTINGS |
| | OR FOUNDATION WALLS. |
| | ANY PIPE THAT PASSES UNDER A FOOTING OR THROUGH A |
| | FOUNDATION WALL SHALL BE PROVIDED WITH A RELIEVING |
| | ARCH, OR A PIPE SLEEVE PIPE SHALL BE BUILT INTO THE |
| | FOUNDATION WALL. THE SLEEVE SHALL BE TWO PIPE SIZES |
| | GREATER THAN THE PIPE PASSING THROUGH THE WALL. |
| | |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |