Plan Review Notes
Plan Review Notes For Permit 14020024
Permit Number 14020024
Review Stop P
Sequence Number 1
Notes
Date Text
2014-02-04 13:42:50PLUMBING PLAN REVIEW
 PERMIT: 13121076/ ISOLATED FOOTINGS & FOUNDATION
 ADD: 8151 OKEECHOBEE BLVD
 CONT: P & T CONSTRUCTION
 TEL: (561)324-8055
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 ARCHITECT: TERCILLA COURTEMANCHE 561-478-4457
 RENE TERCILLA
  
 PLUMBING ENGINEER: RGD CONSULTING ENGINEERS
 561-743-0165
 MICHAEL J. BISHOP
  
 1ST REVIEW
 DATE: TUESDAY FEB. 04/2014
 ACTION: BUILDING PROVISO
  
 1) 2010 CHAPTER 1 ADMINISTRATIVE CODE 105.13.
 SPECIAL PHASED PERIMETER & ISOLATED FOUNDATION PERMIT
 APPROVAL- NO SLAB WORK
  
 AFTER SUBMITTAL OF THE APPROPRIATE CONSTRUCTION
 DOCUMENTS, THE BUILDING OFFICIAL IS AUTHORIZED TO ISSUE
 A PERMIT FOR THE CONSTRUCTION OF FOUNDATIONS OR ANY
 OTHER PART OF A BUILDING OR STRUCTURE BEFORE THE
 CONSTRUCTION DOCUMENTS FOR THE WHOLE BUILDING OR
 STRUCTURE HAVE BEEN SUBMITTED. THE HOLDER OF SUCH
 PERMIT FOR THE FOUNDATION OR OTHER PARTS OF A BUILDING
 OR STRUCTURE SHALL PROCEED AT THE HOLDER'S OWN RISK
 WITH THE BUILDING OPERATION AND WITHOUT ASSURANCE THAT
 A PERMIT FOR THE ENTIRE STRUCTURE WILL BE GRANTED.
 CORRECTIONS MAY BE REQUIRED TO MEET THE REQUIREMENTS OF
 THE TECHNICAL CODES. THIS PROVISION IS ONLY FOR THE
 FLORIDA BUILDING CODE, ALL OTHER AGENCY APPROVALS
 NECESSARY FOR CONSTRUCTION MUST BE SECURED PRIOR TO
 THIS PROVISION BEING APPLIED.
  
 2) 2010 FBC-PLUMBING 305.4 SLEEVES.
 ANNULAR SPACES BETWEEN SLEEVES AND PIPES SHALL BE
 FILLED OR TIGHTLY CAULKED IN AN APPROVED MANNER.
 ANNULAR SPACES BETWEEN SLEEVES AND PIPES IN
 FIRE-RESISTANCE-RATED ASSEMBLIES SHALL BE FILLED OR
 TIGHTLY CAULKED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING.
  
 2010 FBC-PLUMBING 305.5 PIPES THROUGH OR UNDER FOOTINGS
 OR FOUNDATION WALLS.
 ANY PIPE THAT PASSES UNDER A FOOTING OR THROUGH A
 FOUNDATION WALL SHALL BE PROVIDED WITH A RELIEVING
 ARCH, OR A PIPE SLEEVE PIPE SHALL BE BUILT INTO THE
 FOUNDATION WALL. THE SLEEVE SHALL BE TWO PIPE SIZES
 GREATER THAN THE PIPE PASSING THROUGH THE WALL.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  