| 2014-02-04 13:32:36 | BUILDING PLAN REVIEW |
| | PERMIT: 13121076/ ISOLATED FOOTINGS & FOUNDATION |
| | ADD: 8151 OKEECHOBEE BLVD |
| | CONT: P & T CONSTRUCTION |
| | TEL: (561)324-8055 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | ARCHITECT: TERCILLA COURTEMANCHE 561-478-4457 |
| | RENE TERCILLA |
| | |
| | STRUCTURAL: RGD CONSULTING ENGINEERS 561-743-0165 |
| | JAMES FARROR |
| | |
| | 1ST REVIEW |
| | DATE: TUESDAY FEB. 04/2014 |
| | ACTION: BUILDING PROVISO |
| | |
| | 1) 2010 CHAPTER 1 ADMINISTRATIVE CODE 105.13. |
| | SPECIAL PHASED PERIMETER & ISOLATED FOUNDATION PERMIT |
| | APPROVAL- NO SLAB WORK |
| | |
| | AFTER SUBMITTAL OF THE APPROPRIATE CONSTRUCTION |
| | DOCUMENTS, THE BUILDING OFFICIAL IS AUTHORIZED TO ISSUE |
| | A PERMIT FOR THE CONSTRUCTION OF FOUNDATIONS OR ANY |
| | OTHER PART OF A BUILDING OR STRUCTURE BEFORE THE |
| | CONSTRUCTION DOCUMENTS FOR THE WHOLE BUILDING OR |
| | STRUCTURE HAVE BEEN SUBMITTED. THE HOLDER OF SUCH |
| | PERMIT FOR THE FOUNDATION OR OTHER PARTS OF A BUILDING |
| | OR STRUCTURE SHALL PROCEED AT THE HOLDER'S OWN RISK |
| | WITH THE BUILDING OPERATION AND WITHOUT ASSURANCE THAT |
| | A |
| | PERMIT FOR THE ENTIRE STRUCTURE WILL BE GRANTED. |
| | CORRECTIONS MAY BE REQUIRED TO MEET THE REQUIREMENTS OF |
| | THE TECHNICAL CODES. THIS PROVISION IS ONLY FOR THE |
| | FLORIDA BUILDING CODE, ALL OTHER AGENCY APPROVALS |
| | NECESSARY FOR CONSTRUCTION MUST BE SECURED PRIOR TO |
| | THIS PROVISION BEING APPLIED. |
| | |
| | |
| | 2) NOTE THIS PROJECT IS LOCATED IN A A-0 FLOOD ZONE. |
| | FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF ORDINANCES |
| | SECTION 94-546. PLEASE REVIEW CITY ORDINANCE FOR THE |
| | CITY REQUIREMENTS REQUIRE AN ADDITIONAL 6 INCHES OF |
| | ELEVATION. STRUCTURE IS LOCATED IN AN "A0" FLOOD ZONE. |
| | A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. |
| | |
| | FEMA FORM OMB NO. 1660-0008 EXPIRES: |
| | JULY 31,2015 |
| | |
| | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| | REQUIRED: |
| | (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE |
| | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR |
| | HEIGHT BEFORE ISSUANCE OF THE BUILDING PERMIT. |
| | (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND |
| | ELEVATION CERTIFICATE IS REQUIRED |
| | (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| | OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE |
| | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR |
| | ATTENDANT |
| | A/C PADS OR OTHER SLABS FOR GENERATORS ... |
| | |
| | FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR |
| | USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015. |
| | FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE |
| | NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT: |
| | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM |
| | |
| | 3) THE ELEVATOR PIT MAY BE BELOW THE BASE FLOOD |
| | ELEVATION AND WILL NEED TO BE DESIGNED TO RESIST THE |
| | HYDROSTATIC AND HYDRODYNAMIC LOADS AND THE EFFECTS OF |
| | BUOYANCY AS WELL AS BEING FLOOD PROOFED SO THAT SIX |
| | INCHES ABOVE THE BASE FLOOD ELEVATION IS WATER TIGHT |
| | WITH WALLS SUBSTANTIALLY IMPERMEABLE TO THE PASSAGE OF |
| | WATER. WEST PALM MUNI-CODE SECTION 94-546 PROVISIONS |
| | FOR FLOOD HAZARD REDUCTION. |
| | |
| | JAMES A. WITMER CBO |