Plan Review Notes
Plan Review Notes For Permit 14020021
Permit Number 14020021
Review Stop B
Sequence Number 2
Notes
Date Text
2014-02-19 10:47:10****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 COMMENTS FROM PREVIOUS LIST:
  
 1.OK
  
 3. PROPOSED SECOND FLOOR PLAN NOT CLEAR. A DOOR OR GATE
 IS SHOWN BETWEEN THE TWO BUILDINGS. ARE THESE BUILDINGS
 CONNECTED? WHERE DOES THE DOOR/GATE LEAD TO?
  
 2ND REVIEW, IT APPEARS THAT THE GATE IS A PART OF THE
 POOL BARRIER. PLEASE SEE FBC 2010 RESIDENTIAL
 4101.17.1.8 OR REVISE PLAN TO SHOW THAT THE PROPOSED
 GATE IS NOT A PART OF THE POOL BARRIER.
  
 4-6. OK
  
 7. THIS PARCEL IS LOCATED IN FLOOD ZONE A5. PROVIDE A
 COPY OF THE ELEVATION CERTIFICATE OR PROVIDE MORE
 INFORMATION AS TO HOW THIS PROPOSED IMPROVEMENT WILL
 MEET THE REQUIREMENTS OF R322.1.2. ELEVATION
 CERTIFICATE MAY BE SENT VIA EMAIL SO THAT PLAN REVIEW
 CAN BE COMPLETED AT THIS TIME.
  
 ELEVATION CERTIFICATE RECEIVED. AS THE PROPOSED
 IMPROVEMENT IS BELOW THE BFE + FREEBOARD (7' + 6"),
 REVISE PLAN TO INCLUDE DESIGN CRITERIA TO MEET
 REQUIRMENTS OF 322.1.2. IT APPEARS THAT THE
 STAIRS/LANDING/WALL FOOTING ARE BELOW 5'.
  
  