| Plan Review Notes For Permit 14020021 |
| Permit Number |
14020021 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-02-19 10:47:10 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | COMMENTS FROM PREVIOUS LIST: | | | | | | 1.OK | | | | | | 3. PROPOSED SECOND FLOOR PLAN NOT CLEAR. A DOOR OR GATE | | | IS SHOWN BETWEEN THE TWO BUILDINGS. ARE THESE BUILDINGS | | | CONNECTED? WHERE DOES THE DOOR/GATE LEAD TO? | | | | | | 2ND REVIEW, IT APPEARS THAT THE GATE IS A PART OF THE | | | POOL BARRIER. PLEASE SEE FBC 2010 RESIDENTIAL | | | 4101.17.1.8 OR REVISE PLAN TO SHOW THAT THE PROPOSED | | | GATE IS NOT A PART OF THE POOL BARRIER. | | | | | | 4-6. OK | | | | | | 7. THIS PARCEL IS LOCATED IN FLOOD ZONE A5. PROVIDE A | | | COPY OF THE ELEVATION CERTIFICATE OR PROVIDE MORE | | | INFORMATION AS TO HOW THIS PROPOSED IMPROVEMENT WILL | | | MEET THE REQUIREMENTS OF R322.1.2. ELEVATION | | | CERTIFICATE MAY BE SENT VIA EMAIL SO THAT PLAN REVIEW | | | CAN BE COMPLETED AT THIS TIME. | | | | | | ELEVATION CERTIFICATE RECEIVED. AS THE PROPOSED | | | IMPROVEMENT IS BELOW THE BFE + FREEBOARD (7' + 6"), | | | REVISE PLAN TO INCLUDE DESIGN CRITERIA TO MEET | | | REQUIRMENTS OF 322.1.2. IT APPEARS THAT THE | | | STAIRS/LANDING/WALL FOOTING ARE BELOW 5'. | | | | | | |
|