| 2014-04-14 09:04:18 | BUILDING PLAN REVIEW |
| | PERMIT: 14011842 |
| | ADD: 6007 S DIXIE HWY, |
| | CONT: COMMUNITY CONSTRUCTION |
| | TEL: (561)633-2475 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | 3RD REVIEW |
| | DATE: MONDAY APRIL 14/ 2014 |
| | |
| | ACTION: BUILDING PROVISO: |
| | |
| | 1) THE DESIGNER OF RECORD HAS PRINTED NEW NOTES ON THE |
| | PLANS BETWEEN EXISTING FACIAL AND NEW ROOM THAT WAS |
| | CREATED UNDER THIS PERMIT. THE NEW NOTE INDICATES 32 |
| | INCH CLEAR OPENING BETWEEN 2WALLS, THE WALLS SCALE OUT |
| | AT 3'-0" BETWEEN WALLS. THE PARALELL WALLS CAN ONLY BE |
| | REDUCED FOR 24 INCHES AT A CLEAR WIDTH OF 32". |
| | PLEASE REVIEW: |
| | 2010 FL ACCESSIBILITY CODE 403.5.1 CLEAR WIDTH. |
| | EXCEPT AS PROVIDED IN 403.5.2 AND 403.5.3, THE CLEAR |
| | WIDTH OF WALKING SURFACES SHALL BE 36 INCHES (915 MM) |
| | MINIMUM. |
| | EXCEPTION: |
| | THE CLEAR WIDTH SHALL BE PERMITTED TO BE REDUCED TO 32 |
| | INCHES (815 MM) MINIMUM FOR A LENGTH OF 24 INCHES (610 |
| | MM) MAXIMUM PROVIDED THAT REDUCED WIDTH SEGMENTS ARE |
| | SEPARATED BY SEGMENTS THAT ARE 48 INCHES (1220 MM) LONG |
| | MINIMUM AND 36 INCHES (915 MM) WIDE MINIMUM. |
| | |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |