2014-03-17 16:44:16THE ENGINEER'S RESPONSE LETTER IS IN CONFLICT WITH THE
 PLAN PROVIDED PLEASE RESPOND TO THE ORIGINAL COMMENTS
 REPRINTED HERE: THERE IS NO MECHANICAL PLAN PROVIDED,
 HOWEVER THE PROPOSED WORK MAY AFFECT THE VENTILATION
 AND DUCT DESIGN. ACCORDINGLY, PLEASE PROVIDE A
 MECHANICAL PLAN PER FBC 107. ASSURE THE PLAN
 DEMONSTRATES COMPLIANCE WITH FBC-M 403 FOR VENTILATION
 AND OUTSIDE AIR. SEE TABLE 403.3 FOR BEAUTY SALONS.
 ADDITIONALLY, ASSURE THE PLAN DEMONSRATES COMPLIANCE
 FBC-M CHAPTER 6 FOR GENERAL DUCT DESIGN AND BALANCED
 AIR.