| 2014-03-17 16:44:16 | THE ENGINEER'S RESPONSE LETTER IS IN CONFLICT WITH THE | | | PLAN PROVIDED PLEASE RESPOND TO THE ORIGINAL COMMENTS | | | REPRINTED HERE: THERE IS NO MECHANICAL PLAN PROVIDED, | | | HOWEVER THE PROPOSED WORK MAY AFFECT THE VENTILATION | | | AND DUCT DESIGN. ACCORDINGLY, PLEASE PROVIDE A | | | MECHANICAL PLAN PER FBC 107. ASSURE THE PLAN | | | DEMONSTRATES COMPLIANCE WITH FBC-M 403 FOR VENTILATION | | | AND OUTSIDE AIR. SEE TABLE 403.3 FOR BEAUTY SALONS. | | | ADDITIONALLY, ASSURE THE PLAN DEMONSRATES COMPLIANCE | | | FBC-M CHAPTER 6 FOR GENERAL DUCT DESIGN AND BALANCED | | | AIR. |
|