| 2014-03-17 07:52:20 | BUILDING PLAN REVIEW |
| | PERMIT: 14011842 |
| | ADD: 6007 S DIXIE HWY, SUITE ??????? |
| | CONT: COMMUNITY CONSTRUCTION |
| | TEL: (561)633-2475 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: MONDAY MARCH 17/ 2014 |
| | ACTION: DENIED |
| | |
| | 1A) 2ND REQUEST. THE PERMIT APPLICATION INDICATES THE |
| | ADDRESS AS 6007 S DIXIE NO SUITE NUMBER HAS BEEN |
| | PROVIDED ON THE PERMIT APPLICATION NOR PLANS. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION |
| | DOCUMENTS SHALL BE DIMENSIONED AND DRAWN UPON SUITABLE |
| | MATERIA CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED. |
| | |
| | 1B) 2ND REQUEST. THE DESIGNER OF RECORD HAS NOT |
| | INDICATED TO WHAT METHOD OF COMPLIANCE UNDER THE 2010 |
| | EXISTING BUILDING CODE THIS PLANS WAS DEVELOPED. |
| | 101.5 COMPLIANCE METHODS. |
| | THE REPAIR, ALTERATION, CHANGE OF OCCUPANCY, ADDITION |
| | OR RELOCATION OF ALL EXISTING BUILDINGS SHALL COMPLY |
| | WITH ONE OF THE METHODS LISTED IN SECTIONS 101.5.1 |
| | THROUGH 101.5.3 AS SELECTED BY THE APPLICANT. |
| | APPLICATION OF A METHOD SHALL BE THE SOLE BASIS FOR |
| | ASSESSING THE COMPLIANCE OF WORK PERFORMED UNDER A |
| | SINGLE PERMIT UNLESS OTHERWISE APPROVED BY THE CODE |
| | OFFICIAL. SECTIONS 101.5.1 THROUGH 101.5.3 SHALL NOT BE |
| | APPLIED IN COMBINATION WITH EACH OTHER. |
| | |
| | EXCEPTION: SUBJECT TO THE APPROVAL OF THE CODE |
| | OFFICIAL, ALTERATIONS COMPLYING WITH THE LAWS IN |
| | EXISTENCE AT THE TIME THE BUILDING OR THE AFFECTED |
| | PORTION OF THE BUILDING WAS BUILT SHALL BE CONSIDERED |
| | IN COMPLIANCE WITH THE PROVISIONS OF THIS CODE UNLESS |
| | THE BUILDING IS UNDERGOING MORE THAN A LIMITED |
| | STRUCTURAL ALTERATION AS DEFINED IN SECTION 807.4.3. |
| | NEW STRUCTURAL MEMBERS ADDED AS PART OF THE ALTERATION |
| | SHALL COMPLY WITH THE FLORIDA BUILDING CODE, BUILDING. |
| | ALTERATIONS OF EXISTING BUILDINGS IN FLOOD HAZARD AREAS |
| | SHALL COMPLY WITH SECTION 601.3. |
| | |
| | 101.5.1 PRESCRIPTIVE COMPLIANCE METHOD. |
| | REPAIRS, ALTERATIONS, ADDITIONS AND CHANGES OF |
| | OCCUPANCY COMPLYING WITH CHAPTER 3 OF THIS CODE IN |
| | BUILDINGS COMPLYING WITH THE FLORIDA FIRE PREVENTION |
| | CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE |
| | PROVISIONS OF THIS CODE. |
| | |
| | 101.5.2 WORK AREA COMPLIANCE METHOD. |
| | REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY |
| | AND RELOCATED BUILDINGS COMPLYING WITH THE APPLICABLE |
| | REQUIREMENTS OF CHAPTERS 4 THROUGH 12 OF THIS CODE |
| | SHALL BE CONSIDERED IN COMPLIANCE WITH THE PROVISIONS |
| | OF THIS CODE. |
| | |
| | 101.5.3 PERFORMANCE COMPLIANCE METHOD. |
| | REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY |
| | AND RELOCATED BUILDINGS COMPLYING WITH CHAPTER 13 OF |
| | THIS CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE |
| | PROVISIONS OF THIS CODE. |
| | |
| | 2) 2ND REQUEST. DISCREPANCY IN PLANS THE PLANS INDICATE |
| | THAT IT WAS DESIGNED UNDER ASCE 7-07 WHICH IS WIND |
| | DESIGN UNDER THE 2007 FBC, WE ARE CURRENTLY IN THE 2010 |
| | FBC. THE SECOND ISSUE IS THE PLAN IS ALSO DESIGNED |
| | UNDER THE RESIDENTIAL CODE. MERCANTILE AND BUSINESS |
| | OCCUPANCIES FALL UNDER THE 2010 FBC-B. 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 3) 2ND REQUEST. THE PLANS INDICATE A NEW WALL & 32 INCH |
| | WIDE DOOR, PLEASE COMPLY WITH 2010 EXISTING BUILDING |
| | CODE LEVEL II 701.3. COMPLIANCE. ALL NEW CONSTRUCTION |
| | ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY |
| | WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE, |
| | BUILDING. |
| | 2010 FBC-B 1008.1.1 SIZE OF DOORS. |
| | THE MINIMUM WIDTH OF EACH DOOR OPENING SHALL BE |
| | SUFFICIENT FOR THE OCCUPANT LOAD THEREOF AND SHALL |
| | PROVIDE A CLEAR WIDTH OF 32 INCHES (813 MM). CLEAR |
| | OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE |
| | MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP, |
| | WITH THE DOOR OPEN 90 DEGREES (1.57 RAD). TO ACHIEVE |
| | THIS MINIMUM CLEAR MEASUREMENT THE MINIMUM DOOR SIZE |
| | WOULD BE A 2'-10" DOOR. |
| | |
| | AN ENGINEER (DESIGNER OF RECORD) LETTER INDICATES THE |
| | TENANT HAS REMOVED (2) DOORS, THE SUBMITTED PLAN ONLY |
| | SHOWS ONE NEW DOOR. PLEASE PROVIDE WHERE THE LOCATION |
| | OF THE SECOND DOORWAY IS LOCATED. |
| | |
| | A 32 INCH DOOR WAY WOULD PROVIDE A 34 INCH ROUGH |
| | OPENING, WHAT FINISHES ARE GOING TO BE APPLIED TO THE |
| | ROUGH OPENING TO ALLOW FOR A CLEAR OPENING OF 32 |
| | INCHES. |
| | |
| | 4) 2ND REQUEST. THE ENGINEER'S (DESIGNER OF RECORD) |
| | LETTER ALSO INDICATE THE NEW WALLS ARE NO FULL HEIGHT |
| | AND THE NEED OF EMERGENCY BATTERY BACK UP LIGHTS ARE |
| | NOT REQUIRED, NOR IS THERE ANY CHANGE IN THE MECHANICAL |
| | SYSTEM SINCE THE WALLS ARE NOT FULL HEIGHT. THE |
| | DESIGNER OF RECORD HAS NOT PROVIDED THE HEIGHT OF THE |
| | WALLS OR HOW THE WALLS COMPLY WITH 2010 FBC-B TABLE |
| | 1604.3 FOOTNOTE "B" &1607.13. INTERIOR WALLS AND |
| | PARTITIONS. |
| | INTERIOR WALLS AND PARTITIONS THAT EXCEED 6 FEET (1829 |
| | MM) IN HEIGHT, INCLUDING THEIR FINISH MATERIALS, SHALL |
| | HAVE ADEQUATE STRENGTH TO RESIST THE LOADS TO WHICH |
| | THEY ARE SUBJECTED BUT NOT LESS THAN A HORIZONTAL LOAD |
| | OF 5 PSF. |
| | |
| | PLANS ALSO DO NOT PROVIDE COMPLIANCE WITH 2010 FBC-B |
| | 1006.1.6.2 BATTERY-OPERATED ELECTRIC LIGHTS AND OTHER |
| | TYPES OF PORTABLE LAMPS OR LANTERNS SHALL NOT BE USED |
| | FOR PRIMARY ILLUMINATION OF MEANS OF EGRESS. |
| | BATTERY-OPERATED ELECTRIC LIGHTS SHALL BE PERMITTED TO |
| | BE USED AS AN EMERGENCY SOURCE TO THE EXTENT PERMITTED |
| | UNDER SECTION 1006.2.3.4. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | R |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |