2014-02-20 15:08:25THERE IS NO MECHANICAL PLAN PROVIDED, HOWEVER THE
 PROPOSED WORK MAY AFFECT THE VENTILATION AND DUCT
 DESIGN. ACCORDINGLY, PLEASE PROVIDE A MECHANICAL PLAN
 PER FBC 107. ASSURE THE PLAN DEMONSTRATES COMPLIANCE
 WITH FBC-M 403 FOR VENTILATION AND OUTSIDE AIR. SEE
 TABLE 403.3 FOR BEAUTY SALONS. ADDITIONALLY, ASSURE THE
 PLAN DEMONSRATES COMPLIANCE FBC-M CHAPTER 6 FOR GENERAL
 DUCT DESIGN AND BALANCED AIR.