| 2014-02-13 11:51:07 | BUILDING PLAN REVIEW |
| | PERMIT: 14011842 |
| | ADD: 6007 S DIXIE HWY, SUITE ??????? |
| | CONT: COMMUNITY CONSTRUCTION |
| | TEL: (561)633-2475 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. FEB. 13/ 2014 |
| | ACTION: DENIED |
| | |
| | 1A) THE PERMIT APPLICATION INDICATES THE ADDRESS AS |
| | 6007 S DIXIE NO SUITE HAS BEEN PROVIDED ON THE PERMIT |
| | APPLICATION NOR PLANS. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE |
| | DIMENSIONED AND DRAWN UPON SUITABLE |
| | MATERIALCONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED. |
| | |
| | 1B) THE DESIGNER OF RECORD HAS NOT INDICATED TO WHAT |
| | METHOD OF COMPLIANCE UNDER THE 2010 EXISTING BUILDING |
| | CODE THIS PLANS WAS DEVELOPED. |
| | 101.5 COMPLIANCE METHODS. |
| | THE REPAIR, ALTERATION, CHANGE OF OCCUPANCY, ADDITION |
| | OR RELOCATION OF ALL EXISTING BUILDINGS SHALL COMPLY |
| | WITH ONE OF THE METHODS LISTED IN SECTIONS 101.5.1 |
| | THROUGH 101.5.3 AS SELECTED BY THE APPLICANT. |
| | APPLICATION OF A METHOD SHALL BE THE SOLE BASIS FOR |
| | ASSESSING THE COMPLIANCE OF WORK PERFORMED UNDER A |
| | SINGLE PERMIT UNLESS OTHERWISE APPROVED BY THE CODE |
| | OFFICIAL. SECTIONS 101.5.1 THROUGH 101.5.3 SHALL NOT BE |
| | APPLIED IN COMBINATION WITH EACH OTHER. |
| | |
| | EXCEPTION: SUBJECT TO THE APPROVAL OF THE CODE |
| | OFFICIAL, ALTERATIONS COMPLYING WITH THE LAWS IN |
| | EXISTENCE AT THE TIME THE BUILDING OR THE AFFECTED |
| | PORTION OF THE BUILDING WAS BUILT SHALL BE CONSIDERED |
| | IN COMPLIANCE WITH THE PROVISIONS OF THIS CODE UNLESS |
| | THE BUILDING IS UNDERGOING MORE THAN A LIMITED |
| | STRUCTURAL ALTERATION AS DEFINED IN SECTION 807.4.3. |
| | NEW STRUCTURAL MEMBERS ADDED AS PART OF THE ALTERATION |
| | SHALL COMPLY WITH THE FLORIDA BUILDING CODE, BUILDING. |
| | ALTERATIONS OF EXISTING BUILDINGS IN FLOOD HAZARD AREAS |
| | SHALL COMPLY WITH SECTION 601.3. |
| | |
| | 101.5.1 PRESCRIPTIVE COMPLIANCE METHOD. |
| | REPAIRS, ALTERATIONS, ADDITIONS AND CHANGES OF |
| | OCCUPANCY COMPLYING WITH CHAPTER 3 OF THIS CODE IN |
| | BUILDINGS COMPLYING WITH THE FLORIDA FIRE PREVENTION |
| | CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE |
| | PROVISIONS OF THIS CODE. |
| | |
| | 101.5.2 WORK AREA COMPLIANCE METHOD. |
| | REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY |
| | AND RELOCATED BUILDINGS COMPLYING WITH THE APPLICABLE |
| | REQUIREMENTS OF CHAPTERS 4 THROUGH 12 OF THIS CODE |
| | SHALL BE CONSIDERED IN COMPLIANCE WITH THE PROVISIONS |
| | OF THIS CODE. |
| | |
| | 101.5.3 PERFORMANCE COMPLIANCE METHOD. |
| | REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY |
| | AND RELOCATED BUILDINGS COMPLYING WITH CHAPTER 13 OF |
| | THIS CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE |
| | PROVISIONS OF THIS CODE. |
| | |
| | 2) DISCREPANCY IN PLANS THE PLANS INDICATE THAT IT WAS |
| | DESIGNED UNDER ASCE 7-07 WHICH IS WIND DESIGN UNDER THE |
| | 2007 FBC, WE ARE CURRENTLY IN THE 2010 FBC. THE SECOND |
| | ISSUE IS THE PLAN IS ALSO DESIGNED UNDER THE |
| | RESIDENTIAL CODE. MERCANTILE AND BUSINESS OCCUPANCIES |
| | FALL UNDER THE 2010 FBC-B. 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 3) THE PLANS INDICATE A NEW WALL & 32 INCH WIDE DOOR, |
| | PLEASE COMPLY WITH 2010 EXISTING BUILDING CODE LEVEL II |
| | 701.3. COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, |
| | COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| | REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING. |
| | 2010 FBC-B 1008.1.1 SIZE OF DOORS. |
| | THE MINIMUM WIDTH OF EACH DOOR OPENING SHALL BE |
| | SUFFICIENT FOR THE OCCUPANT LOAD THEREOF AND SHALL |
| | PROVIDE A CLEAR WIDTH OF 32 INCHES (813 MM). CLEAR |
| | OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE |
| | MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP, |
| | WITH THE DOOR OPEN 90 DEGREES (1.57 RAD). TO ACHIEVE |
| | THIS MINIMUM CLEAR MEASUREMENT THE MINIMUM DOOR SIZE |
| | WOULD BE A 2'-10" DOOR. |
| | |
| | 4) PLANS ALSO DO NOT PROVIDE COMPLIANCE WITH 2010 FBC-B |
| | 1006.1.6.2 BATTERY-OPERATED ELECTRIC LIGHTS AND OTHER |
| | TYPES OF PORTABLE LAMPS OR LANTERNS SHALL NOT BE USED |
| | FOR PRIMARY ILLUMINATION OF MEANS OF EGRESS. |
| | BATTERY-OPERATED ELECTRIC LIGHTS SHALL BE PERMITTED TO |
| | BE USED AS AN EMERGENCY SOURCE TO THE EXTENT PERMITTED |
| | UNDER SECTION 1006.2.3.4. |
| | JAMES A. WITMER CBO |