Plan Review Notes
Plan Review Notes For Permit 14011764
Permit Number 14011764
Review Stop B
Sequence Number 1
Notes
Date Text
2014-02-08 08:36:14 
 BUILDING PLAN REVIEW
 PERMIT: 14011764
 ADD: 4121 PARKER AVE
 CONT: QUALITY HOME TEAM
 TEL: (561)704-1810
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 LEVEL II ALTERATION NOT DECLARED.
  
 1ST REVIEW
 DATE: SATURDAY FEB. 08/2014
 ACTION: DENIED
  
 1) THE DESIGNER OF RECORD HAS NOT INDICATED UNDER WHAT
 METHOD OF DESIGN WAS UNDERTAKEN FOR THIS PLAN AND
 COMPLIANCE WITH:
 2010 FL EXST BLDG. CODE 101.5 COMPLIANCE METHODS.
 THE REPAIR, ALTERATION, CHANGE OF OCCUPANCY, ADDITION
 OR RELOCATION OF ALL EXISTING BUILDINGS SHALL COMPLY
 WITH ONE OF THE METHODS LISTED IN SECTIONS 101.5.1
 THROUGH 101.5.3 AS SELECTED BY THE APPLICANT.
 APPLICATION OF A METHOD SHALL BE THE SOLE BASIS FOR
 ASSESSING THE COMPLIANCE OF WORK PERFORMED UNDER A
 SINGLE PERMIT UNLESS OTHERWISE APPROVED BY THE CODE
 OFFICIAL. SECTIONS 101.5.1 THROUGH 101.5.3 SHALL NOT BE
 APPLIED IN COMBINATION WITH EACH OTHER.
  
 2A) IS THIS A CHANGE OF OCCUPANCY? EXST BUILDING CODE
 CHANGE OF OCCUPANCY. A CHANGE IN THE PURPOSE OR LEVEL
 OF ACTIVITY WITHIN A BUILDING THAT INVOLVES A CHANGE IN
 APPLICATION OF THE REQUIREMENTS OF THIS CODE.
 2B) ARE THERE MORE TENANTS ON THIS FLOOR? TENANT
 SEPERATION WALLS REQUIRE 1 HR SEPERATION IN
 UNSPRINKLERED BUILDINGS. 2010 FBC-B 709.1.6.
  
 3) 705.7 MEANS-OF-EGRESS LIGHTING. MEANS-OF-EGRESS
 LIGHTING SHALL BE IN ACCORDANCE WITH THIS SECTION, AS
 APPLICABLE. 705.7.1 ARTIFICIAL LIGHTING REQUIRED. MEANS
 OF EGRESS IN ALL WORK AREAS SHALL BE PROVIDED WITH
 ARTIFICIAL LIGHTING IN ACCORDANCE WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 PLEASE PROVIDE EMERGENCY BACK UP LIGHTING TO THE EXIT.
 2010 FBC-B 1006.1.6 SOURCES OF ILLUMINATION. 1006.1.6.2
 BATTERY-OPERATED ELECTRIC LIGHTS AND OTHER TYPES OF
 PORTABLE LAMPS OR LANTERNS SHALL NOT BE USED FOR
 PRIMARY ILLUMINATION OF MEANS OF EGRESS.
 BATTERY-OPERATED ELECTRIC LIGHTS SHALL BE PERMITTED TO
 BE USED AS AN EMERGENCY SOURCE TO THE EXTENT PERMITTED
 UNDER SECTION 1006.2.3.4.
  
 4) PLANS DO NOT INDICATE COMPLIANCE WITH PORTABLE FIRE
 EXTINGUISHERS, 2010 FBC-B EVERY 75'-0" 906.2 GENERAL
 REQUIREMENTS. PORTABLE FIRE EXTINGUISHERS SHALL BE
 SELECTED, INSTALLED AND MAINTAINED IN ACCORDANCE WITH
 THIS SECTION AND NFPA 10.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  