| | BUILDING PLAN REVIEW |
| | PERMIT: 14011764 |
| | ADD: 4121 PARKER AVE |
| | CONT: QUALITY HOME TEAM |
| | TEL: (561)704-1810 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | LEVEL II ALTERATION NOT DECLARED. |
| | |
| | 1ST REVIEW |
| | DATE: SATURDAY FEB. 08/2014 |
| | ACTION: DENIED |
| | |
| | 1) THE DESIGNER OF RECORD HAS NOT INDICATED UNDER WHAT |
| | METHOD OF DESIGN WAS UNDERTAKEN FOR THIS PLAN AND |
| | COMPLIANCE WITH: |
| | 2010 FL EXST BLDG. CODE 101.5 COMPLIANCE METHODS. |
| | THE REPAIR, ALTERATION, CHANGE OF OCCUPANCY, ADDITION |
| | OR RELOCATION OF ALL EXISTING BUILDINGS SHALL COMPLY |
| | WITH ONE OF THE METHODS LISTED IN SECTIONS 101.5.1 |
| | THROUGH 101.5.3 AS SELECTED BY THE APPLICANT. |
| | APPLICATION OF A METHOD SHALL BE THE SOLE BASIS FOR |
| | ASSESSING THE COMPLIANCE OF WORK PERFORMED UNDER A |
| | SINGLE PERMIT UNLESS OTHERWISE APPROVED BY THE CODE |
| | OFFICIAL. SECTIONS 101.5.1 THROUGH 101.5.3 SHALL NOT BE |
| | APPLIED IN COMBINATION WITH EACH OTHER. |
| | |
| | 2A) IS THIS A CHANGE OF OCCUPANCY? EXST BUILDING CODE |
| | CHANGE OF OCCUPANCY. A CHANGE IN THE PURPOSE OR LEVEL |
| | OF ACTIVITY WITHIN A BUILDING THAT INVOLVES A CHANGE IN |
| | APPLICATION OF THE REQUIREMENTS OF THIS CODE. |
| | 2B) ARE THERE MORE TENANTS ON THIS FLOOR? TENANT |
| | SEPERATION WALLS REQUIRE 1 HR SEPERATION IN |
| | UNSPRINKLERED BUILDINGS. 2010 FBC-B 709.1.6. |
| | |
| | 3) 705.7 MEANS-OF-EGRESS LIGHTING. MEANS-OF-EGRESS |
| | LIGHTING SHALL BE IN ACCORDANCE WITH THIS SECTION, AS |
| | APPLICABLE. 705.7.1 ARTIFICIAL LIGHTING REQUIRED. MEANS |
| | OF EGRESS IN ALL WORK AREAS SHALL BE PROVIDED WITH |
| | ARTIFICIAL LIGHTING IN ACCORDANCE WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | PLEASE PROVIDE EMERGENCY BACK UP LIGHTING TO THE EXIT. |
| | 2010 FBC-B 1006.1.6 SOURCES OF ILLUMINATION. 1006.1.6.2 |
| | BATTERY-OPERATED ELECTRIC LIGHTS AND OTHER TYPES OF |
| | PORTABLE LAMPS OR LANTERNS SHALL NOT BE USED FOR |
| | PRIMARY ILLUMINATION OF MEANS OF EGRESS. |
| | BATTERY-OPERATED ELECTRIC LIGHTS SHALL BE PERMITTED TO |
| | BE USED AS AN EMERGENCY SOURCE TO THE EXTENT PERMITTED |
| | UNDER SECTION 1006.2.3.4. |
| | |
| | 4) PLANS DO NOT INDICATE COMPLIANCE WITH PORTABLE FIRE |
| | EXTINGUISHERS, 2010 FBC-B EVERY 75'-0" 906.2 GENERAL |
| | REQUIREMENTS. PORTABLE FIRE EXTINGUISHERS SHALL BE |
| | SELECTED, INSTALLED AND MAINTAINED IN ACCORDANCE WITH |
| | THIS SECTION AND NFPA 10. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |