| Plan Review Notes For Permit 14011702 |
| Permit Number |
14011702 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-02-24 15:13:41 | PLANS CALL FOR NEW HVAC AS WELL AS OTHER ELECTRICAL | | | WORK NOT ADDRESSED ON THE PERMIT APPLICATION. PLEASE | | | REVISE THE PLANS TO DEFINE THE ACTUAL SCOPE OF WORK. IF | | | THE SAME SHEET IS TO BE RE-SUBMITTED, MARK THE EXISTING | | | AS SUCH AND INDICATE THE NEW AS NEW WORK. FURTHERMORE, | | | THE SUBMITTED DRAWINGS CALL FOR WORK ON A GENERATOR NOT | | | ADDRESSED ON THE PERMIT EITHER. THE HVAC CONDENSING | | | UNITS DO NOT INDICATE THAT THEY COMPLY WITH NEC 210.63. | | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | | CONTACT: | | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | PH: (561) 805-6718, EMAIL: [email protected] | | | |
|