| Date |
Text |
| 2014-02-04 10:37:35 | PLUMBING PLAN REVIEW |
| | PERMIT: 14011700 |
| | ADD: 221 CLEMATIS ST |
| | CONT: GALFA CEE CO. |
| | TEL: (561)249-2608 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUESDAY, FEB. 04/2014 |
| | ACTION: DENIED |
| | |
| | 1) SHEET P-1: |
| | 1A) RESTROOM # 107 IS SHOWN TO HAVE A LAVOTORY, SHOWER |
| | AND WATER CLOSET, PLEASE NOTE THAT THE SINK S-2 FROM |
| | ROOM # 107 IS WET VENTING THE WATER CLOSET SEE FBC-P |
| | 909.2.1. |
| | THE SINK S-2 SHOULD BE ON A INDIVIDUAL VENT 907.1. IN |
| | THE STRISTEST SINCE OF THE CODE WET VENTS ARE ONLY USED |
| | IN BATHROOM GROUPS, WHICH WE HAVE. BY DEFINITION OF |
| | BATHROOM GROUPS WET VENTS ARE NOT SUPPOSE TO BE USED IN |
| | RESTROOM SINCE RESTROOMS ARE COMMERCIAL NOT |
| | RESIDENTIAL. |
| | |
| | 1B) THIS COMMENT WILL BE A COMMON COMMENT FOR ALL |
| | SHOWERS, THE FLOOR SYSTEM IN THIS BUILDING IS |
| | STRUCTURAL CONCRETE SLAB, HOW WILL THE SHOWER PAN/ |
| | LINER MEET COMPLIANCE WITH FBC-P SECTION 417.5.2 SHOWER |
| | LINING. FLOORS UNDER SHOWER COMPARTMENTS, EXCEPT WHERE |
| | PREFABRICATED RECEPTORS HAVE BEEN PROVIDED, SHALL BE |
| | LINED AND MADE WATER TIGHT UTILIZING MATERIAL COMPLYING |
| | WITH SECTIONS 417.5.2.1 THROUGH 417.5.2.5. SUCH LINERS |
| | SHALL TURN UP ON ALL SIDES AT LEAST 2 INCHES (51 MM) |
| | ABOVE THE FINISHED THRESHOLD LEVEL. LINERS SHALL BE |
| | RECESSED AND FASTENED TO AN APPROVED BACKING SO AS NOT |
| | TO OCCUPY THE SPACE REQUIRED FOR WALL COVERING, AND |
| | SHALL NOT BE NAILED OR PERFORATED AT ANY POINT LESS |
| | THAN 1 INCH (25 MM) ABOVE THE FINISHED THRESHOLD. |
| | LINERS SHALL BE PITCHED ONE-FOURTH UNIT VERTICAL IN 12 |
| | UNITS HORIZONTAL (2-PERCENT SLOPE) AND SHALL BE SLOPED |
| | TOWARD THE FIXTURE DRAINS AND BE SECURELY FASTENED TO |
| | THE WASTE OUTLET AT THE SEEPAGE ENTRANCE, MAKING A |
| | WATER-TIGHT JOINT BETWEEN THE LINER AND THE OUTLET. THE |
| | COMPLETED LINER SHALL BE TESTED IN ACCORDANCE WITH |
| | SECTION 312.9. |
| | |
| | 1C) THIS COMMENT WILL BE COMMON FOR ALL SHOWERS, THE |
| | PLUMBING ISOMETRIC PLANS INDICATE A SD & FD DRAIN. THE |
| | PLUMBING FIXTURE & EQUIPMENT SCHEDULE LIST: |
| | FD AS A FLOOR DRAIN AT SHOWER |
| | SD AS A DECK -O-DRAIN SLOTTED PVC DRAIN, PLEASE PROVIDE |
| | THE MANUFACTURES SPEC ON THE PITICULAAR PRODUCT THAT |
| | WILL BE INSTALLED, PLEASE PROVIDE A DETAIL OF HOW THE |
| | SHOWER LINING WILL REMAIN WATER TIGHT WITH THE JOINT |
| | FOR THE DRAIN, DURING THE SHOWER LINER TEST. ALSO |
| | PROVIDE IN THE DETAIL COMPLIANCE WITH THE ACCESSIBILITY |
| | CODE 608.7 THRESHOLDS. |
| | |
| | 1D) THIS COMMENT WILL BE COMMON FOR ALL SHOWERS,SHEET |
| | P1 SHOWS ALL SHOWERS TO BE TRAPED AND WASTE TO BE 2 |
| | INCH, PLEASE NOTE SHEET P-2 SH-1 AND SH-2 BOTH INDICATE |
| | 2.5 GPM WITH FLOW RESTRICTOR SHOWER VALUE, IS THE |
| | RESTRICTOR A WASHER THAT CAN BE REMOVED TO ALLOW |
| | AGREATER FLOW? THE FEAR IS UNDER THESE CONDITIONS THE |
| | DRAIN MEETS THE DEMAND, TABLE 709.1 ALLOWS 2 INCH TRAP |
| | AND DRAIN UP TO 5.7 GPM OR LESS, A 3 INCH TRAP AND |
| | DRAIN WILL HANDLE FROM 12.3 GPM TO 25.8 GPM WITH THIS |
| | BEING A ACCESSIBLE SHOWER AND NO CURB THIS IS OF |
| | CONCERN BUT CODE COMPLIANT. |
| | |
| | 1E) BATHROOM GROUP 108 THE ISOMETRIC PLAN SHOWS THE |
| | WASHING MACHINE TIEING INTOOR PAST THE BATHROOM |
| | HORIZONTAL WET VENT WITH A 2" DRAIN LINE, PLEASE REVIEW |
| | TABLE 709.1 |
| | FOR BOTH RESIDENTIAL AND COMMERCIAL CLOTHES WASHERS SEE |
| | FOOTNOTE "G" SEE SECTION 406.3 FOR SIZING REQUIREMENTS |
| | FOR FIXTURE DRAIN, BRANCH DRAIN, AND DRAINAGE STACK FOR |
| | AN AUTOMATIC CLOTHES WASHER STANDPIPE. |
| | 406.3 WASTE CONNECTION. THE WASTE FROM AN AUTOMATIC |
| | CLOTHES WASHER SHALL DISCHARGE THROUGH AN AIR BREAK |
| | INTO A STANDPIPE IN ACCORDANCE WITH SECTION 802.4 OR |
| | INTO A LAUNDRY SINK. THE TRAP AND FIXTURE DRAIN FOR AN |
| | AUTOMATIC CLOTHES WASHER STANDPIPE SHALL BE A MINIMUM |
| | OF 2 INCHES (51 MM) IN DIAMETER. THE AUTOMATIC CLOTHES |
| | WASHER FIXTURE DRAIN SHALL CONNECT TO A BRANCH DRAIN OR |
| | DRAINAGE STACK A MINIMUM OF 3 INCHES (76 MM) IN |
| | DIAMETER. |
| | |
| | 2) SHEET P-2: |
| | 2A) TH PLUMBING FIXTURE & EQUIPMENT SCHEDULE INDICATES |
| | THE USE OF TWH TANKLESS WATER HEATERS PLEASE PROVIDE |
| | THE MANUFACTURERS MANUAL & SPECIFICATION FOR COMPLIANCE |
| | WITH |
| | SECTION 504 SAFETY DEVICES OF THE PLUMBING CODE. |
| | |
| | 2B) ON BOTH THE HOT & COLD WATER SUPPLY PIPING WATER |
| | HAMMER AIR CHAMBERS ARE SHOWN, PLEASE PROVIDE |
| | COMPLIANCE WITH FBC-P 604.9 WATER HAMMER. |
| | THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM |
| | SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER |
| | HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED |
| | WHERE QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER |
| | ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE |
| | MANUFACTURER?S SPECIFICATIONS. WATER-HAMMER ARRESTORS |
| | SHALL CONFORM TO ASSE 1010. |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |