| Plan Review Notes For Permit 14011700 |
| Permit Number |
14011700 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-02-26 15:18:35 | PLAN DENIED | | | 1) PROVIDE GRILL SIZE ON THE PLAN. | | | PER SECTION 107 FBC 2010 | | | 2) PROVIDE VOLUME DAMPERS AT DUCT OR GRILL | | | 3) PROVIDE A DETAIL FROM THE ENGINEER ON THE | | | CONDENSER STAND TIE DOWN TO ROOF AND | | | CONDENSER TIE DOWN TO STAND . | | | PER SECTION 103.12 WIND RESISTANCE 2010 FBC (M) | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | |
|