| Plan Review Notes For Permit 14011700 |
| Permit Number |
14011700 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-02-04 13:14:02 | 14011700 | | | 221 CLEMATIS STREET | | | GYM AND MASSAGE | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | VERIFY THE ELECTRICAL SERVICE MAINS FOR THIS BUILDING | | | ARE SIX OR LESS AND GROUPED IN ONE LOCATION. SHOW ALL | | | METERS, GROUNDING, MAIN DISCONNECTS AND PANEL BOARDS | | | FOR THE BUILDING SERVICE.. | | | NEC 230.2, 230.71, 230.72 | | | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION | | | FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING | | | MEANS. NEC 110.22, 110.16, 110.22 | | | | | | PROVIDE A DESIGNATED CLEAR WORKING SPACE AROUND THE | | | ELECTRICAL SERVICE EQUIPMENT AND PANEL BOARDS. NEC | | | 215.5, 110.26 | | | | | | VERIFY THE EQUIPMENT FAULT CURRENT RATING IS SUFFICIENT | | | AT NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE | | | INTERRUPTED. NEC 110.9 | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS REVIEW | | | | | | | | 2014-02-04 12:27:24 | BY RL |
|