2014-02-04 08:17:36BUILDING PLAN REVIEW
 PERMIT: 14011700
 ADD: 221 CLEMATIS ST SUITE # MISSING SUITE NUMBER/ 3RD
 FLOOR
 CONT: GALFA CEE CO.
 TEL: (561)249-2608
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUESDAY, FEB. 04/2014
 ACTION: DENIED
  
 ***** MISSING SUITE NUMBER/ 3RD FLOOR *******
  
 1) COVERSHEET A.1 INDICATES UNDER THE HEADING OCCUPANT
 LOAD A BUSINESS OCCUPANCY AND NO DECLARED OCCUPANCY FOR
 THE EXERCISE ROOM. THE EXERCISE ROOM SQUARE FEET IS
 1357 SQ FT/ 50= 28 OCCUPANTS. NEITHER A3 OR LS-1 SHOW
 EQUIPMENT IN THE EXERCISE ROOM, IF THERE IS NO
 EQUIPMENT SHOWN THEN 15 SQ FT IS USED SEE TABLE FBC-B
 1004.1.1.
  
 2) SHEET A-3 INDICATES DOOR # 107 AS A OUT SWING DOOR,
 NEXT TO THE LATCH SIDE OF THE DOOR IT APPEARS TO BE
 APPROXIMATELY 12 INCHES, 2010 FL ACCESS CODE SECTION
 404.2.1 AND TABLE 404.2.1 REQUIRES 18 INCHES ON THE
 LATCH SIDE OF THE DOOR.
  
 3SHEET A-3 SHOWER ROOM # 107 & SHEET A-5 SHOWER ROOM
 107 INDICATE THIS ROOM TO BE AN ACCESSIBLE INDIVIDUAL
 SHOWER ROOM. THE SHOWER ENCLOSURE DOES NOT INDICATE
 COMPLIANCE WITH 2010 FL ACCESS CODE 608.7 THRESHOLDS.
 THRESHOLDS IN ROLL-IN TYPE SHOWER COMPARTMENTS SHALL BE
 1/2 INCH (13 MM) HIGH MAXIMUM IN ACCORDANCE WITH 303.
 IN TRANSFER TYPE SHOWER COMPARTMENTS, THRESHOLDS 1/2
 INCH (13 MM) HIGH MAXIMUM SHALL BE BEVELED, ROUNDED, OR
 VERTICAL.
  
 4) SHEET A-3 SHOWER ROOM # 107 IS THE ACCESSIBLE SHOWER
 IN THIS CLUSTER OF RESTROOMS, IT WILL NEED TO COMPLY
 WITH 2010 FL ACCESS CODE 213.2 TOILET ROOMS AND BATHING
 ROOMS.
 EXCEPTION # 3. WHERE MULTIPLE SINGLE USER PORTABLE
 TOILET OR BATHING UNITS ARE CLUSTERED AT A SINGLE
 LOCATION, NO MORE THAN 5 PERCENT OF THE TOILET UNITS
 AND BATHING UNITS AT EACH CLUSTER SHALL BE REQUIRED TO
 COMPLY WITH 603. PORTABLE TOILET UNITS AND BATHING
 UNITS COMPLYING WITH 603 SHALL BE IDENTIFIED BY THE
 INTERNATIONAL SYMBOL OF ACCESSIBILITY COMPLYING WITH
 703.7.2.1. 703.7.2.1 INTERNATIONAL SYMBOL OF
 ACCESSIBILITY. THE INTERNATIONAL SYMBOL OF
 ACCESSIBILITY SHALL COMPLY WITH ALL REQUIREMENTS OF
 SECTION 703 & FIGURE 703.7.2.1.
  
 5) SHEET A-3 ALSO WILL NEED TO MEET THE REQUIREMENTS OF
 2010 FL ACCESS CODE 213.2 TOILET ROOMS AND BATHING
 ROOMS. EXCEPTION # 3. WHERE MULTIPLE SINGLE USER
 PORTABLE TOILET OR BATHING UNITS ARE CLUSTERED AT A
 SINGLE LOCATION, NO MORE THAN 5 PERCENT OF THE TOILET
 UNITS AND BATHING UNITS AT EACH CLUSTER SHALL BE
 REQUIRED TO COMPLY WITH 603.
  
 ADVISORY 213.2 TOILET ROOMS AND BATHING ROOMS
 EXCEPTIONS 3 AND 4.
 A ?CLUSTER? IS A GROUP OF TOILET ROOMS PROXIMATE TO ONE
 ANOTHER. GENERALLY, TOILET ROOMS IN A CLUSTER ARE
 WITHIN SIGHT OF, OR ADJACENT TO, ONE ANOTHER.
  
 6) SHEET A3 AND A5 SHOWER ROOM # 111 IS NOT CONSIDERED
 WITHIN THE CLUSTER AND WOULD ALSO NEED TO COMPLY WITH
 SECTION 2010 FL ACCESS CODE SECTION 213.2 TOILET ROOMS
 AND BATHING ROOMS.
 WHERE TOILET ROOMS ARE PROVIDED, EACH TOILET ROOM SHALL
 COMPLY WITH 603. WHERE BATHING ROOMS ARE PROVIDED, EACH
 BATHING ROOM SHALL COMPLY WITH 603.
 ADVISORY 213.2 TOILET ROOMS AND BATHING ROOMS.
 THESE REQUIREMENTS ALLOW THE USE OF UNISEX (OR
 SINGLE-USER) TOILET ROOMS IN ALTERATIONS WHEN TECHNICAL
 INFEASIBILITY CAN BE DEMONSTRATED. UNISEX TOILET ROOMS
 BENEFIT PEOPLE WHO USE OPPOSITE SEX PERSONAL CARE
 ASSISTANTS. FOR THIS REASON, IT IS ADVANTAGEOUS TO
 INSTALL UNISEX TOILET ROOMS IN ADDITION TO ACCESSIBLE
 SINGLE-SEX TOILET ROOMS IN NEW FACILITIES.
  
 7) SHEET A6 THE KITCHEN/ BREAK ROOM SINK WILL NEED TO
 COMPLY WITH 2010 FL ACCESS CODE SECTIONS:
 7A) 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED.
 306.3.2 MAXIMUM DEPTH.
 KNEE CLEARANCE SHALL EXTEND 25 INCHES (635 MM) MAXIMUM
 UNDER AN ELEMENT AT 9 INCHES (230 MM) ABOVE THE FINISH
 FLOOR OR GROUND.
  
 306.3.3 MINIMUM REQUIRED DEPTH.
 WHERE KNEE CLEARANCE IS REQUIRED UNDER AN ELEMENT AS
 PART OF A CLEAR FLOOR SPACE, THE KNEE CLEARANCE SHALL
 BE 11 INCHES (280 MM) DEEP MINIMUM AT 9 INCHES (230 MM)
 ABOVE THE FINISH FLOOR OR GROUND, AND 8 INCHES (205 MM)
 DEEP MINIMUM AT 27 INCHES (685 MM) ABOVE THE FINISH
 FLOOR OR GROUND.
  
 7B) 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 8) SHEET A-6 ROOM FINISH SCHEDULE, SHOWER ROOMS, NOTE #
 3, INDICATES PROVIDE MOISTURE RESISTANT GYPSUM
 WALLBOARD AT THE CEILINGS. PLEASE REVIEW THE USE
 LIMITATIONS FOR 2509.3 LIMITATIONS. NOTE THIS IS FOR
 BACKING BOARD!!!!!
 WATER-RESISTANT GYPSUM BACKING BOARD SHALL NOT BE USED
 IN THE FOLLOWING LOCATIONS:
 1. OVER A VAPOR RETARDER IN SHOWER OR BATHTUB
 COMPARTMENTS.
 2. WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN
 AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY.
 3. ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 INCHES
 (305 MM) O.C. FOR 1/2-INCH-THICK (12.7 MM)
 WATER-RESISTANT GYPSUM BACKING BOARD AND MORE THAN 16
 INCHES (406 MM) O.C. FOR 5/8-INCH-THICK (15.9 MM)
 WATER-RESISTANT GYPSUM BACKING BOARD.
  
 9) : WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  