| 2014-03-05 11:44:52 | THE FOLLOWING SHALL BE ADDRESS AND OR CORRECTED FOR A | | | SATISFACTORY ELECTRICAL REVIEW: | | | 1. SUBMIT A RISER DIAGRAM INDICATING THE SERVICE AS | | | EXISTING AND THE PROPOSED IF ANY CHANGES ARE TO BE | | | MADE, ALONG WITH PROPER LOAD CALCS. | | | 2. PROVIDE A PANEL SCHEDULE INDICATING THE CIRCUITS FOR | | | THE NEW AREA. | | | 3. INCLUDE CIRCUIT DESIGNATIONS ON THE FLOOR PLAN. | | | 4. ALL OUTLETS SHALL HAVE GFCI PROTECTION. | | | 5. COMPLIANCE WITH THE NEC ARC-FAULT REQUIREMENTS IS | | | NECESSARY. | | | 6. SHOW COMPLETE AND PROPER GROUNDING ELECTRODE SYSTEM | | | AS PER NEC 250. | | | | | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | | CONTACT: | | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | PH: (561) 805-6718, EMAIL: [email protected] | | | | | | | | | RETURNED TO BIN R 20 |
|