Plan Review Notes
Plan Review Notes For Permit 14011597
Permit Number 14011597
Review Stop B
Sequence Number 2
Notes
Date Text
2014-05-30 08:00:53****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 COMMENT FROM PREVIOUS LIST:
  
 1. PROVIDE A STRUCTURAL DETAIL FOR PROPOSED
 IMPROVEMENT. THIS SHOULD INCLUDE WIND DESIGN CRITERIA
 FBC 1609. ARCHITECTURAL SHEETS REFER TO STRUCTURALS,
 BUT THEY WERE NOT SUBMITTED.
  
 2ND REVIEW - STRUCTURAL DETAILS WERE PROVIDED AS
 REQUESTED, BUT I WAS UNABLE TO LOCATE WIND DESIGN
 CRITERIA, SEE FBC 1603.1.4. IF THIS IS ON THE PLAN,
 PLEASE SEND AN EMAIL ADVISING AS TO WHERE THIS
 INFORMATION CAN BE LOCATED.
  
 IF THIS IS NOT ON THE PLAN, EITHER REVISE THE PLAN TO
 INCLUDE WIND DESIGN CRITERIA AND RESUBMIT, OR THE
 DESIGNER CAN PROVIDE THE INFORMATION IN LETTER FORM (ON
 LETTERHEAD; SIGNED, SEALED, AND DATED) AND EMAIL TO ME.
 THE ORIGINAL WILL BE REQUIRED AT TIME OF PERMIT PICKUP.
  
  