| Plan Review Notes For Permit 14011595 |
| Permit Number |
14011595 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2014-09-13 15:56:13 | TO MISC. 2 FOR BUILDING REVIEW. | | 2014-09-13 15:39:31 | DATE: 9/13/2014 | | | PROJECT: UNIVERSAL CHURCH | | | PERMIT#: 14011595 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: PROVISO | | | | | | 1) 505.2.4 EXTERIOR LIGHTING CONTROLS. | | | LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN | | | SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF | | | TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT | | | IS AVAILABLE OR WHEN THE LIGHTING IS NOT REQUIRED | | | DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR | | | DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A | | | COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN | | | ASTRONOMICAL TIME SWITCH. | | | | | | 2) 2010 FBC-BUILDING SECTION 1609 | | | PROVIDE WIND LOAD CALCULATIONS FOR THE NEW LIGHT POLES | | | INCLUDING THE LUMINAIRES. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|