| Plan Review Notes For Permit 14011585 |
| Permit Number |
14011585 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-03-18 10:11:33 | REVISION BUILDING REVIEW COMMENTS. | | | | | | 1- ENERGY CALCULATIONS SUBMITTED ARE TAKING THE CROSS | | | VENTILATION CREDIT. ARCHITECT OF RECORD TO REVISE PLANS | | | SHOWING COMPLIANCE WITH THE CROSS VENTILATION CREDIT AS | | | REQUIRED BY SEC. 405.6.4 AND SEC. 103.2.2 OF 2010 | | | FBC-ENERGY CONSERVATION. | | | | | | 2- REVISE THE ENERGY CALCULATIONS. WINDOWS OVERHANG | | | DEPTH AND SEPARATION SHOWN ON PAGE 3 OF 5 DON'T MATCH | | | THE ACTUAL OVERHANG DEPTH AND SEPARATION AS SHOWN ON | | | PLANS. REVISE AS REQUIRED. SEC. 103.2.1.1.2 OF 2010 | | | FBC-ENERGY CONSERVATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|