| Plan Review Notes For Permit 14011582 |
| Permit Number |
14011582 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-02-10 14:26:58 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 | | | [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2010 | | | | | | 1. FAC61G15-23.002, DOCUMENTS PREPARED BY AN ENGINEER | | | (EASTERN ENGINEERING GROUP) AND SUBMITTED FOR PUBLIC | | | RECORD ARE TO BE SIGNED, SEALED DATED ORIGINALS. AN | | | INDEX SHEET MAY BE USED. THE TITLE BLOCK IS TO INCLUDE | | | CERTIFICATE OF AUTHORIZATION (COVER SHEET). OTHER | | | SHEETS DO NOT INCLUDE THE ENGINEER'S PRINTED NAME, | | | LICENSE NUMBER, OR THE CERTIFICATE OF AUTHORIZATION. IF | | | AN INDEX SHEET IS NOT USED, EACH SHEET IS TO BE SIGNED | | | AND SEALED. PLEASE SEE FAC61G15-23 REGARDING INDEX | | | SHEET REQUIREMENTS. | | | | | | 2. THE PRODUCT APPROVALS SUBMITTED ARE NOT THE SAME AS | | | SUBMITTED UNDER PERMIT 13070818. THEREFORE, A REVISION | | | UNDER THAT PERMIT NUMBER IS REQUIRED. PLEASE PROVIDE A | | | COMPLETED REVISION FORM. | | | | | | 3. IT IS NOT CLEAR WHY A SEPARATE PERMIT FOR STOREFRONT | | | IS BEING REQUESTED. THIS SCOPE IS INCLUDED UNDER THE | | | MASTER PERMIT. IF GENERAL CONTRACTOR AND THE STOREFRONT | | | SUB CONTRACTOR BOTH WISH FOR YOU TO HAVE A SEPARATE | | | PERMIT, A PERMIT WILL BE ISSUED AS A BUILDING SUB | | | PERMIT. OTHERWISE, THE PERMIT APPLICATION NUMBER | | | GENERATED WILL BE CHANGED TO A REVISION TRACKING | | | NUMBER. | | | | | | 4. A REVIEW BY DESIGNER OF RECORD IS REQUIRED, FBC 107. | | | THIS MAY BE IN THE FORM OF A SHOP DRAWING REVIEW STAMP | | | OR LETTER. | | | | | | | | | | | | | | | |
|