| 2014-02-03 15:15:45 | 2010 FBC |
| | |
| | REVISION IS DENIED |
| | |
| | 1) THE REVISED ENERGY CALCULATIONS THAT WERE SUBMITTED |
| | ARE WORST CASE. THE 2010 FBC ENERGY CONSERVATION |
| | REQUIRES THAT THE ACTUAL ORIENTATION OF THE BUILDING BE |
| | USED TO DETERMINE THE HEATING AND COOLING LOADS AND |
| | EQUIPMENT SIZE. PLEASE CORRECT. SEE SECTION 403.6.1. |
| | |
| | 2) THE REQUIRED INSULATION FOR THE FLOOR AREA ABOVE THE |
| | OPEN ENTRY IS NOT LISTED ON THE ENERGY CALCULATIONS. |
| | PLEASE CORRECT. |
| | |
| | 3) LABEL THE FLOOR PLANS ON THE MECHANICAL PLANS TO |
| | INDICATE THE FIRST FLOOR AND SECOND FLOOR. CITY |
| | AMENDMENTS 107.2.1 |
| | |
| | 4) A 10" DUCT IS SHOWN ON THE PLANS TO SUPPLY AIR TO |
| | THE MASTER BEDROOM SUITE. THE 10" TRANSFER DUCT FOR THE |
| | RETURN AIR IS TOO SMALL. FBCR M1602.4 BALANCED RETURN |
| | AIR REQUIRES TRANSFER DUCTS TO BE 1.5 TIMES THE CROSS |
| | SECTIONAL AREA OF THE SUPPLY DUCT. PLEASE CORRECT. |
| | |
| | 5) CLARIFY THE LOCATION OF THE RETURN AIR GRILL FOR THE |
| | SECOND FLOOR AIR HANDLER. THE APPROVED PLANS SPECIFY |
| | THE RETURN AREA THROUGH A LOUVERED DOOR ON THE A/H |
| | CLOSET. CITY AMENDMENTS 107.2.1 |
| | |
| | 6) THE BTU TOTAL LISTED ON THE PLANS FOR AC #2 OF |
| | 24,300 DOES NOT MATCH THE 23,400 ON THE LOAD |
| | CALCULATIONS AND ENERGY CALCULATIONS. FBCR M1401.3 |
| | PLEASE CORRECT. |
| | |
| | WHEN RE-SUBMITTING, TELL THE CLERK THAT YOU ARE |
| | RE-SUBMITTING A DENIED REVISION AND USE THE REVISION |
| | NUMBER. THIS WILL SAVE YOU FROM PAYING AND ADDITIONAL |
| | $100.00 REVISION FEE AND YOU WILL ONLY BE CHARGED THE |
| | $50.00 PER PAGE FEE. |
| | |