E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-04-10 14:20:23 | 14011502 | | | 7731 SOUTH DIXIE | | | PLANET FITNESS | | | 2ND REVIEW | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | THE ELECTRICAL SERVICE AS NOTED ON SHEET E4.1 INDICATES | | | A 600A, 277/480 VOLT SERVICE WHICH FEEDS AN EXISTING | | | 800A, 120/208 VOLT MDB. REVISE PLANS TO SHOW CORRECT | | | VOLTAGE AND PHASE. NEC 215.5 | | | | | | THE PLANS ARE NOT CLEAR REGARDING THE LIMITATIONS | | | PROVIDED WITHIN THE CODE FOR THE NUMBER OF SERVICES | | | ALLOWED TO THE BUILDING AND THE LOCATIONS OF THE MAIN | | | DISCONNECTS FOR THE EXISTING AND NEW OCCUPANCIES. FIRE | | | SEPARATIONS ARE ONE METHOD TO PROVIDE SEPARATION WITHIN | | | STRUCTURES FOR OCCUPANCIES REQUIRING THEIR OWN ELECTRIC | | | SERVICE. THE PLAN NEEDS TO VERIFY THAT THERE IS ONLY | | | ONE POINT OF SERVICE TO EACH BUILDING AND THAT THE | | | ELECTRICAL SERVICE MAINS FOR EACH SERVICE ARE SIX OR | | | LESS AND GROUPED IN ONE LOCATION. NEC 230.2, 230.71, | | | 230.72 | | | | | | | | | NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR, FIRE | | | ALARM SYSTEMS, SECURITY AND DATA SYSTEMS. | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS REVIEW | | | 561-373-3701 | | | | | | |
|