| 2014-01-29 16:45:25 | 7731 SOUTH DIXIE HIGHWAY |
| | PERMIT #14011502 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | SHEET A6.0: FINISH GB-2 INDICATES SOME SORT OF |
| | STYROFOAM. THE INTERIOR FINISH MATERIALS FOR WALLS AND |
| | CEILINGS SHALL MEET THE SMOKE DEVELOPMENT (0-450) AND |
| | FLAME SPREAD (76-200) REQUIREMENTS FOR CLASS C INTERIOR |
| | FINISHES PER NFPA 101. |
| | |
| | SHEET A6.0: FLOOR COVERINGS (RUBBER FLOORING), OTHER |
| | THAN CARPET, THAT MAY REPRESENT AN UNUSUAL HAZARD SHALL |
| | HAVE A CRITICAL RADIANT FLUX OF AT LEAST 0.1 W/CM2 |
| | (RESISTANCE TO FLAME PROPAGATION) AS PER NFPA 253. |
| | |
| | GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW |
| | EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE |
| | BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE |
| | ORDERED FROM WWW.KNOXBOX.COM. |
| | |
| | GENERAL: PROVIDE DRAWING NOTE INDICATING ALL |
| | CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO THE |
| | REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS |
| | SHALL BE REMOVED FROM THE SITE DAILY. SMOKING SHALL BE |
| | PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL |
| | OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| | SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE |
| | RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. |
| | |
| | GENERAL: PROVIDE DRAWING NOTE INDICATING, "FIRE |
| | PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE SUBMITTED BY EMAIL ([email protected]) OR IN WRITING |
| | (FAX: 561-804-4774) AND APPROVED BY THE OFFICE OF THE |
| | FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY." |
| | |
| | GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT |
| | DOORS WITH EXIT SIGNS. |
| | |
| | GENERAL: FOR ISSUANCE OF A GENERAL BUILDING PERMIT, |
| | SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING CODE |
| | REQUIRES SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS |
| | FOR THE DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC |
| | FIRE SPRINKLERS. AFTER THE BUILDING PERMIT HAS BEEN |
| | ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP |
| | DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION |
| | DOCUMENTS) FOR A SUB-PERMIT. |
| | |