| Plan Review Notes For Permit 14011471 |
| Permit Number |
14011471 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-01-27 10:07:01 | PLUMBING PROVISO: | | | AIR ADMITTANCE VALVE ON KITCHEN SINK: | | | 917.3.2 RELIEF VENT. | | | WHERE THE HORIZONTAL BRANCH IS LOCATED MORE THAN FOUR | | | BRANCH INTERVALS FROM THE TOP OF THE STACK, | | | THE HORIZONTAL BRANCH SHALL BE PROVIDED WITH A RELIEF | | | VENT THAT SHALL CONNECT TO A VENT STACK OR | | | STACK VENT, OR EXTEND OUTDOORS TO THE OPEN AIR. THE | | | RELIEF VENT SHALL CONNECT TO THE HORIZONTAL BRANCH | | | DRAIN BETWEEN THE STACK AND THE MOST DOWNSTREAM FIXTURE | | | DRAIN CONNECTED TO THE HORIZONTAL BRANCH | | | DRAIN. THE RELIEF VENT SHALL BE SIZED IN ACCORDANCE | | | WITH SECTION 916.2 AND INSTALLED IN ACCORDANCE WITH | | | SECTION 905. THE RELIEF VENT SHALL BE PERMITTED TO | | | SERVE AS THE VENT FOR OTHER FIXTURES. |
|