| Plan Review Notes For Permit 14011470 |
| Permit Number |
14011470 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-04-26 12:09:48 | DENIED BY BUILDING | | | | | | 1) TWO COPIES OF HEATING AND COOLING EQUIPMENT SIZING | | | CALCULATIONS WERE SUBMITTED. HOWEVER, THE ENERGY | | | CALCULATION COMPLIANCE FORMS THAT WERE REQUESTED IN THE | | | FIRST REVIEW WERE NOT SUBMITTED. PLEASE SUBMIT TWO SETS | | | OF ENERGY CALCS. THAT HAVE BEEN SIGNED BY THE PREPARER | | | AND THE OWNER AGENT. (SUBMIT TWO COPIES OF THE ENERGY | | | COMPLIANCE FORMS FOR ONE OF THE APPROVED METHODS OF | | | COMPLIANCE REQUIRED BY THE 2010 FBC ENERGY CONSERVATION | | | SECTION 103.2.1.1.) | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|