| Plan Review Notes For Permit 14011450 |
| Permit Number |
14011450 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-04-19 10:22:54 | PLUMBING PLAN REVIEW | | | PERMIT: 14011450 | | | ADD: 315 9TH ST | | | CONT: BENITZ BUILDING LLC | | | TEL: (561)659-4024 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | DATE: SAT. APRIL 19/2014 | | | ACTION: DENIED | | | | | | 1) PLANS SUBMITTED HAVE THE BATHROOM THAT IS SHOWN TO | | | BE ELINATED ON SHEET 107.2.1.3 DISCREPANCY IN PLANS. | | | | | | 2) PLANS SUBMITTED ONLY SHOW THE ORIGINAL WATER | | | FOUNTAIN LOCATION NOT THE SECOND LOCATION FOR THE OTHER | | | REQUIRED DRINKING FOUNTAIN. 107.2.1.3 DISCREPANCY IN | | | PLANS. | | | | | | | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] |
|