| Plan Review Notes For Permit 14011422 |
| Permit Number |
14011422 |
|
| Review Stop |
G |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2014-11-15 07:09:22 | 1) PLEASE SUBMIT ADDITIONAL INFORMATION AS TO HOW YOU | | | ARRIVED AT YOUR CALCULATIONS FOR THE COMBUSTION AIR FOR | | | THE APPLIANCES IN ACCORDANCE WITH THE 2010 FGC | | | SEC.304.5.1 OR 304.5.2. SHOW THE METHOD USED AND THE | | | CALCULATIONS, AIR INFILTRATION RATE, ETC. | | | 2) PLEASE SUPPLY THE FOLLOWING ITEMS FOR THE GAS RISER: | | | A) THE LONGEST LENGTH OF PIPING FROM THE POINT OGF | | | DELIVERYTO THE MOST REMOTE OUTLET. | | | B) THE DELIVERY PRESSURE OF THE SYSTEM | | | C) THE APPLICABLE SIZING TABLE FROM THE 2010 FL. GAS | | | CODE. | | | (ITEMS A,B,C, WERE OVERLOOKED IN MY PREVIOUS REVIEW.) | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|