| 2014-10-21 13:39:37 | 1)SHT. S.2 - DETAILS #1 & 2 - THE MEASUREMENT FROM THE |
| | FINISHED FLOOR TO THE TOP OF THE WATER CLOSET SEAT |
| | SHALL BE 17' - 19" PER THE 2010 FL. ACCESSIBILITY CODE |
| | SEC.604.4. |
| | 2) THE HEIGHT OF THE RIM OF THE LAVATORY TO THE |
| | FINISHED FLOR SHALL BE A MAX. OF 34". SHOW THIS ON THE |
| | PLAN. |
| | 3) SHOW THE DIMENSION FROM THE FINISHED FLOOR TO THE |
| | BOTTOM OF THE MIRROR. COMPLY W/ FAC SEC. 603.3. |
| | 4) SUBMIT CALCULATIONS FOR THE SIZING OF THE GREASE |
| | TRAP. COMPLY W/ FPC SEC.103.3.4. |
| | 5) THE CLEANOUT FOR THE GREASE TRAP IS INSTALLED IN THE |
| | OPPOSITE DIRECTION OF FLOW. |
| | 6) SHT. P.4 - THE SERVICE SINK IS LISTED ON THE |
| | SANITARY ISER ISOMETRIC AS "EXISTING" BUT THE PLAN |
| | SHOWS IT AS NEW. CLARIFY. |
| | 7) THE SERVICE SINK SHALL NOT BE MORE THAN 12 FT. FROM |
| | A VENTED LINE PER TABLE 906.1. |
| | 8) A DRINKING FOUNTAIN IS REQD. PER TABLE 403.1. YOU |
| | HAVE LISTED AN OCCUPANT LOAD OF 69 PERSONS SO THE |
| | EXCEPTION IN FOOTNOTE F DOES NOT APPLY. |
| | 9) SHT. P.4 - SHOWS THE GREASE TRAP TO BE OF CONCRETE |
| | BUT THE SPECS ARE FOR A METAL TANK. CLARIFY. SUBMIT |
| | MANUF. SPECIFICATIONS FOR THE GREASE INTERCEPTOR TO BE |
| | USED. |
| | 10) SHT. P.5 SHOWS THE RELIEF LINE DISCHARGING TO A |
| | FLOOR DRAIN BUT THERE IS NO FLOOR DRAIN IN THIS AREA. |
| | CLARIFY. |
| | 11) YOU ARE CLASSIFYING THIS AS AN A-2 OCCUPANCY? HOW |
| | CAN THIS BE? THIS APPEARS TO BE MORE OF A MERCANTILE |
| | OCCUPANCY THAN AN ASSEMBLY. CLARIFY. |
| | |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |