| 2014-07-28 08:03:40 | PLUMBNG PLAN REVIEW |
| | PERMIT: 14011422 |
| | ADD: 847 SOUTHERN BLVD. |
| | CONT: CARLOS GONZALEZ |
| | TEL: (561)386-8217 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: MON. JULY 28/2014 |
| | ACTION: DENIED |
| | |
| | 1) 3RD REQUEST. 2010 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1.3 PLUMBING |
| | 1. MINIMUM PLUMBING FACILITIES PROVIDE THE OCCUPANT |
| | LOAD AND COMPLIANCE WITH 2010 PLUMB TABLE 403.1 PLEASE |
| | NOTE THE SERVICE SINK ON THE EXTERIOR OF THE BUILDING |
| | WILL NEED TO SHOW TYING INTO THE GREASY WASTE BEFOR THE |
| | GREASE INTERCEPTOR. THIS INFORMATION WAS ON THE PLANS |
| | SUBMITTED |
| | 4/ 09/14 BY THE DESIGNER OF RECORD, NOW IT IS MISSING. |
| | |
| | 2) 3RD REQUEST. . THE LAST SET OF PLANS REVIEW # 2 |
| | LISTED BY NUMBER, (1,2,3,4,5,6,...) SHEET 3 OF 4 |
| | INDICATES EITHER FIXTURES OR APPLIANCES 1-17, THE PLANS |
| | DO NOT IDENTIFY IF THESE ARE FIXTURES REQUIRING FLOOR |
| | SINKS (THREE COMPARTMENT SINK, HAND SINK, REFRIGARATED |
| | CASES, ICE MAKING MACHINES, COFFE URNS, AND DRINK |
| | DISPENSORS. THEY ARE NOT IDENTIFIED. NOW THE NUMBERS |
| | ARE TOTALLY MISSING AND THE USE OF THESE FIXTURES AND |
| | OR APPLIANCES: |
| | 2010 FBC-P 802.1 WHERE REQUIRED. |
| | FOOD-HANDLING EQUIPMENT AND CLEAR-WATER WASTE SHALL |
| | DISCHARGE THROUGH AN INDIRECT WASTE PIPE AS SPECIFIED |
| | IN SECTIONS 802.1.1 THROUGH 802.1.8. ALL HEALTH-CARE |
| | RELATED FIXTURES, DEVICES AND EQUIPMENT SHALL DISCHARGE |
| | TO THE DRAINAGE SYSTEM THROUGH AN INDIRECT WASTE PIPE |
| | BY MEANS OF AN AIR GAP IN ACCORDANCE WITH THIS CHAPTER |
| | AND SECTION 713.3. FIXTURES NOT REQUIRED BY THIS |
| | SECTION TO BE INDIRECTLY CONNECTED SHALL BE DIRECTLY |
| | CONNECTED TO THE PLUMBING SYSTEM IN ACCORDANCE WITH |
| | CHAPTER 7. |
| | |
| | 802.1.1 FOOD HANDLING. |
| | EQUIPMENT AND FIXTURES UTILIZED FOR THE STORAGE, |
| | PREPARATION AND HANDLING OF FOOD SHALL DISCHARGE |
| | THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN AIR GAP. |
| | . |
| | |
| | 3. WATER SUPPLY PIPING, THE ISSUE WITH THIS PLAN IS ON |
| | THE POTABLE WATER SUPPLY ICE MAKING MACHINES, COFFE |
| | URNS, AND DRINK DISPENSORS. |
| | 2010 FBC-P 608.16.1 BEVERAGE DISPENSERS. THE WATER |
| | SUPPLY CONNECTION TO BEVERAGE DISPENSERS SHALL BE |
| | PROTECTED AGAINST BACKFLOW BY A BACKFLOW PREVENTER |
| | CONFORMING TO ASSE 1022 OR BY AN AIR GAP.THE PORTION OF |
| | THE BACKFLOW PREVENTER DEVICE DOWNSTREAM FROM THE |
| | SECOND CHECK VALVE AND THE PIPING DOWNSTREAM THEREFROM |
| | SHALL NOT BE AFFECTED BY CARBON DIOXIDE GAS. |
| | |
| | |
| | |
| | 4. 3RD REQUEST - SANITARY DRAINAGE THE ISOMETRIC |
| | DRAWING SHOWS THE HAND SINKS AND 3 COMPARTMENT SINKS |
| | WITH A DIRECT CONNECTION TO THE WASTE NO FLOOR SINK FOR |
| | A INDIRECT CONNECTION 802.1.1, THE OTHER ISSUE WITH THE |
| | PLANS IS NO INDIVIDUAL DRAINS ARE SHOWN AS DRAWN, FOR |
| | THE FLOOR SINKS, VENTS WILL NEED TO BE ILLUSTRATED. |
| | FLOOR DRAIN IN THE KITCHEN WILL NEED A TRAP PRIMER |
| | SINCE IT IS NOT BEING FED BY A FIXTURE (1002.4 TRAP |
| | SEALS), |
| | THE HAND SINK THAT BACKS UP TO THE STORAGE ROOM SHOULD |
| | NOT BE ON THE GREASY WASTE (P 1003.3.1), AGAIN THE |
| | SERVICE SINK ON THE EXTERIOR OF THE BUILDING IS NOT |
| | PART OF THE GREASY WASTE. IF THIS FIXTURE IS A CAN WASH |
| | IT TO SHOULD BE ON THE GREASY WASTE AND THE REQUIREMENT |
| | FOR A SERVICE |
| | SINK WILL STILL NEED TO BE MET. TABLE 403. USE A2 |
| | RESTARAUNT/ DELI. |
| | |
| | |
| | 5.COMPLIED. WATER HEATERS |
| | |
| | 6. 3RD REQUEST THE FLOOR SINK, NOT SHOWN FOR THE 3 |
| | COMPARTMENT SINK WILL NEED TO BE VENTED, THE FLOW |
| | CONTROL FOR THE GREASE INTERCEPTOR WILL ALSO NEED TO BE |
| | VENTED, SEE INDIVIDUAL VENTS 607.1 & 1003.3.4.2. |
| | |
| | 7). 3RD BACK FLOW PREVENTION 608.3 DEVICES, |
| | APPURTENANCES, APPLIANCES AND APPARATUS. ALL DEVICES, |
| | APPURTENANCES, APPLIANCES AND APPARATUS INTENDED TO |
| | SERVE SOME SPECIAL FUNCTION, COOLING, OR STORAGE OF ICE |
| | OR FOODS, |
| | |
| | 8) 3RD 604.9 WATER HAMMER. THE FLOW VELOCITY OF THE |
| | WATER DISTRIBUTION SYSTEM SHALL BE CONTROLLED TO REDUCE |
| | THE POSSIBILITY OF WATER HAMMER. A WATER-HAMMER |
| | ARRESTOR SHALL BE INSTALLED WHERE QUICK-CLOSING VALVES |
| | ARE UTILIZED. WATER-HAMMER ARRESTORS SHALL BE INSTALLED |
| | IN ACCORDANCE WITH THE MANUFACTURER?S SPECIFICATIONS. |
| | WATER-HAMMER ARRESTORS SHALL CONFORM TO ASSE 1010 |
| | |
| | 9. 3RD PLUMBING RISER MISSING FLOOR SINKS FBC-P 802.1. |
| | 8 FOOD UTENSILS, DISHES, POTS AND PANS SINKS. SINKS |
| | USED FOR THE WASHING, RINSING OR SANITIZING OF |
| | UTENSILS, DISHES, POTS, PANS OR SERVICEWARE USED IN THE |
| | PREPARATION, SERVING OR EATING OF FOOD SHALL DISCHARGE |
| | INDIRECTLY THROUGH AN AIR GAP OR AN AIR BREAK OR |
| | DIRECTLY CONNECT TO THE DRAINAGE SYSTEM. |
| | |
| | 802.1.7 COMMERCIAL DISHWASHING MACHINES. |
| | THE DISCHARGE FROM A COMMERCIAL DISHWASHING MACHINE |
| | SHALL BE THROUGH AN AIR GAP OR AIR BREAK INTO A |
| | STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH SECTION |
| | 802.2. |
| | |
| | 802.1.5 NONPOTABLE CLEAR-WATER WASTE. |
| | WHERE DEVICES AND EQUIPMENT SUCH AS PROCESS TANKS, |
| | FILTERS, DRIPS AND BOILERS DISCHARGE NONPOTABLE WATER |
| | TO THE BUILDING DRAINAGE SYSTEM, THE DISCHARGE SHALL BE |
| | THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN AIR BREAK |
| | OR AN AIR GAP. |
| | |
| | 10) 3RD REQUET THE GREASE INTERCEPTOR IS NOW INDICATED |
| | AS A 750 GALLON CONCRETE VAULT TYPE GREASE INTERCEPTOR. |
| | CONCRETE VAULT INTERCEPTORS ARE |
| | SIZED BY USING THE FOLLOWING 2010 FBC-P 1003.5.1. |
| | PLEASE PROVIDE THE MANUFACTURERS SPECIFICATION SHOWING |
| | COMPLIANCE WITH 1003.3.5. |
| | |
| | 2ND GREASE INTERCEPTOR SHEET 2 INDICATES THE USE OF A |
| | ATLANTIC METAL WORKS G1-100 PLEASE PROVIDE THE |
| | MANUFACTURERS SPECS ON THIS UNIT. |
| | PLEASE PROVIDE SIZING FOR INTERCEPTOR WITH ONE OF THESE |
| | METHODS 1003.3.4 GREASE INTERCEPTORS AND AUTOMATIC |
| | GREASE REMOVAL DEVICES. |
| | THE GREASY WASTE SHOULD ALSO INCLUDE THE FLOOR DRAIN |
| | AND SERVIDE SINK/ MOP SINK. |
| | THE PLANS DO NOT INCLUDE THE LOCATION OF THE GREASE |
| | INTERCEPTOR. |
| | |
| | GREASE INTERCEPTORS AND AUTOMATIC GREASE REMOVAL |
| | DEVICES SHALL BE SIZED IN ACCORDANCE WITH PDI G101, |
| | ASME A112.14.3 APPENDIX A, OR ASME A112.14.4. GREASE |
| | INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL |
| | BE DESIGNED AND TESTED IN ACCORDANCE WITH PDI G101, |
| | ASME A112.14.3 OR ASME A112.14.4. GREASE INTERCEPTORS |
| | AND AUTOMATIC GREASE REMOVAL DEVICES SHALL BE INSTALLED |
| | IN ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |