| 2014-07-28 06:50:16 | FUEL GAS PLAN REVIEW |
| | PERMIT: 14011422 |
| | ADD: 847 SOUTHERN BLVD. |
| | CONT: CARLOS GONZALEZ |
| | TEL: (561)386-8217 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: MON. JULY 28/ 2014 |
| | ACTION: DENIED |
| | |
| | NOTE: APPLY FOR A FUEL GAS PERMIT SEPERATELY. |
| | |
| | NOTICE TO DESIGNER OF RECORD!!!!: CHAPTER 553.80(2)(B) |
| | FLORIDA STATUTES STATES THAT A LOCAL GOVERNMENT SHALL |
| | IMPOSE A FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF |
| | PLANS ARE REJECTED THREE OR MORE TIMES FOR REPEATED |
| | FAILURE TO CORRECT A CODE VIOLATION. |
| | |
| | 1) SHEET P.3 INDICATES THE PRESENCE OF PROPOSED GAS |
| | LINES, SHEET S3 INDICATES THE USE OF GAS APPLIANCES |
| | FRYER, FLAT TOP, STOVE & OVEN. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 2010 |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING |
| | OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA |
| | AND DOCUMENTS: |
| | 107.3.5.1.5 GAS |
| | GAS PERMIT APPLICATION REQUIREMENTS |
| | |
| | EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL |
| | BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING |
| | IN THE CITY OF WEST PALM BEACH: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL |
| | CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER |
| | FBC-2010 FUEL GAS. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS |
| | STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | |
| | 3. TYPE OF GAS, (LP OR NATURAL). |
| | |
| | 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON |
| | THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35) |
| | |
| | 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, |
| | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING |
| | AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ? |
| | USE OF CAPACITY SECTION A.3.1(4) |
| | |
| | 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE |
| | FBC-2010 FUEL GAS CODE SEC. 304 |
| | |
| | 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010 |
| | FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 |
| | PSI. |
| | |
| | 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND |
| | TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS CODE |
| | SEC. 502 THRU 505. |
| | |
| | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2010 FUEL GAS SEC. 402.2 |
| | |