| Date |
Text |
| 2014-04-22 17:25:49 | PLUMBNG PLAN REVIEW |
| | PERMIT: 14011422 |
| | ADD: 847 SOUTHERN BLVD. |
| | CONT: CARLOS GONZALEZ |
| | TEL: (561)386-8217 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: TUES. APRIL 22/2014 |
| | ACTION: DENIED |
| | |
| | 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: PROVIDE A COMPLETE |
| | FLOOR PLAN OF THE BUILDING AND ENTENDED USAGE. |
| | THE EXAMINATION OF THE DOCUMENTS BY THE |
| | BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM |
| | CRITERIA AND DOCUMENTS: |
| | 107.3.5.1.3 PLUMBING |
| | 1. MINIMUM PLUMBING FACILITIES PROVIDE THE OCCUPANT |
| | LOAD AND COMPLIANCE WITH 2010 PLUMB TABLE 403.1 PLEASE |
| | NOTE THE SERVICE SINK ON THE EXTERIOR OF THE BUILDING |
| | WILL NEED TO SHOW TYING INTO THE GREASY WASTE BEFOR THE |
| | GREASE INTERCEPTOR. |
| | 2. FIXTURE REQUIREMENTS SHEET 3 OF 4 INDICATES EITHER |
| | FIXTURES OR APPLIANCES 1-17, THE PLANS DO NOT IDENTIFY |
| | IF THESE ARE FIXTURES REQUIRING FLOOR SINKS (THREE |
| | COMPARTMENT SINK, HAND SINK, REFRIGARATED CASES, ICE |
| | MAKING MACHINES, COFFE URNS, AND DRINK DISPENSORS. 2010 |
| | FBC-P 802.1.1. |
| | 3.COMPLIED. WATER SUPPLY PIPING |
| | 4. 2ND REQUEST - SANITARY DRAINAGE THE ISOMETRIC |
| | DRAWING SHOWS THE HAND SINKS AND 2 COMPARTMENT SINKS |
| | WITH A DIRECT CONNECTION TO THE WASTE NO FLOOR SINK FOR |
| | A INDIRECT CONNECTION 802.1.1, THE OTHER ISSUE WITH THE |
| | PLANS IS NO INDIVIDUAL DRAINS ARE SHOWN AS DRAWN, FOR |
| | THE FLOOR SINKS VENTS WILL NEED TO BE ILLUSTRATED. |
| | FLOOR DRAIN IN THE KITCHEN WILL NEED A TRAP PRIMER |
| | SINCE IT IS NOT BEING FED BY A FIXTURE (1002.4 TRAP |
| | SEALS), |
| | 5.COMPLIED. WATER HEATERS |
| | 6. VENTS AS DRAWN NOW THE 3 COMPARTMENT SINK, AND ALL |
| | HAND SINKS ARE BEING VENTED BY A SINGLE VENT , THE |
| | FLOOR SINKS WILL NEED TO BE VENTED, THE FLOW CONTROL |
| | FOR THE GREASE INTERCEPTOR WILL ALSO NEED TO BE VENTED, |
| | SEE INDIVIDUAL VENTS 607.1 & 1003.3.4.2. |
| | 7). BACK FLOW PREVENTION 608.3 DEVICES, APPURTENANCES, |
| | APPLIANCES AND APPARATUS. ALL DEVICES, APPURTENANCES, |
| | APPLIANCES AND APPARATUS INTENDED TO SERVE SOME SPECIAL |
| | FUNCTION, COOLING, OR STORAGE OF ICE OR FOODS, |
| | 8) 604.9 WATER HAMMER. THE FLOW VELOCITY OF THE WATER |
| | DISTRIBUTION SYSTEM SHALL BE CONTROLLED TO REDUCE THE |
| | POSSIBILITY OF WATER HAMMER. A WATER-HAMMER ARRESTOR |
| | SHALL BE INSTALLED WHERE QUICK-CLOSING VALVES ARE |
| | UTILIZED. WATER-HAMMER ARRESTORS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH THE MANUFACTURER?S SPECIFICATIONS. |
| | WATER-HAMMER ARRESTORS SHALL CONFORM TO ASSE 1010 |
| | 9. CORRECTED PLUMBING RISER |
| | |
| | 2) 2ND REQUEST GREASE INTERCEPTOR SHEET 2 INDICATES THE |
| | USE OF A ATLANTIC METAL WORKS G1-100 PLEASE PROVIDE THE |
| | MANUFACTURERS SPECS ON THIS UNIT. |
| | PLEASE PROVIDE SIZING FOR INTERCEPTOR WITH ONE OF THESE |
| | METHODS 1003.3.4 GREASE INTERCEPTORS AND AUTOMATIC |
| | GREASE REMOVAL DEVICES. |
| | THE GREASY WASTE SHOULD ALSO INCLUDE THE FLOOR DRAIN |
| | AND SERVIDE SINK/ MOP SINK. |
| | THE PLANS DO NOT INCLUDE THE LOCATION OF THE GREASE |
| | INTERCEPTOR. |
| | |
| | GREASE INTERCEPTORS AND AUTOMATIC GREASE REMOVAL |
| | DEVICES SHALL BE SIZED IN ACCORDANCE WITH PDI G101, |
| | ASME A112.14.3 APPENDIX A, OR ASME A112.14.4. GREASE |
| | INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL |
| | BE DESIGNED AND TESTED IN ACCORDANCE WITH PDI G101, |
| | ASME A112.14.3 OR ASME A112.14.4. GREASE INTERCEPTORS |
| | AND AUTOMATIC GREASE REMOVAL DEVICES SHALL BE INSTALLED |
| | IN ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS. |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |