| 2014-04-24 13:47:24 | 847 SOUTHERN BOULEVARD |
| | PERMIT #14011422 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | NEW COMMENT - SHEET 4 OF 4: PROVIDE A DISPLAY LAYOUT OF |
| | THE NEW AND EXISTING "DISPLAY ROOMS" SHOWING AISLE |
| | WIDTHS, SHELVING, SEATING, ETC. |
| | |
| | REVIEW #2 COMMENT - SHEET 4 OF 4: NO FIRE RATED DOOR |
| | SHOWN ON EXISTING STORAGE ROOM. |
| | ORIGINAL COMMENT: PER SECTION 8.7, ANY AREA (STORAGE) |
| | HAVING A DEGREE OF HAZARD GREATER THAN NORMAL TO THE |
| | GENERAL OCCUPANCY (MERCANTILE) OF THE BUILDING, SHALL |
| | BE SEPARATED FROM NON-STORAGE AREAS WITH A 1-HOUR |
| | FIRE-RATED BARRIER OR BE PROTECTED WITH AN AUTOMATIC |
| | SPRINKLER SYSTEM. DOORS SHALL BE SELF CLOSING, POSITIVE |
| | LATCHING, AND FIRE-RATED FOR AT LEAST 45-MINUTES. |
| | |
| | REPEAT COMMENT: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED |
| | EXIT DOORS WITH EXIT SIGNS. |
| | |
| | REPEAT COMMENT: PER SECTION 7.2.1.5.9, THE LOCK/LATCH |
| | RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE DOOR |
| | WITH NOT MORE THAN ONE RELEASING OPERATION. THE |
| | RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF |
| | OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING |
| | CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF |
| | BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE |
| | TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST |
| | TO OPERATE. THUMB-TURN LOCK TO BE EQUIPPED WITH AN |
| | "OPEN/LOCKED" INDICATOR WINDOW (SUCH AS ADAMS RITE 4089 |
| | OR SIMILAR). |
| | |
| | |