| 2014-04-22 16:50:19 | BUILDING PLAN REVIEW |
| | PERMIT: 14011422 |
| | ADD: 847 SOUTHERN BLVD. |
| | CONT: CARLOS GONZALEZ |
| | TEL: (561)386-8217 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: TUES. APRIL 22/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) 2ND REQUEST . ADDITIONAL INFORMATION IS REQUIRED, |
| | THE PBC PROPERTY APPRAISERS WEB SITE LIST THIS PROPERTY |
| | AS A CONVENIENCE STORE WITH GAS PUMPS? |
| | WILL THE GAS PUMPS CONTINUE TO BE IN OPERATION? THE |
| | PLANS INDICATE THIS BUILDING IS TO BE CONVERTED INTO A |
| | CAFETERIA, THIS WOULD MEANS A RESTARAUNT THE PLANS DO |
| | NOT SHOW A DINING ROOM. |
| | |
| | 2) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS THE |
| | EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL |
| | SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND |
| | DOCUMENTS: A FLOOR PLAN |
| | . 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 1.COMPLIED MERCANILE <50 OCCUPANTS. OCCUPANCY GROUP AND |
| | SPECIAL OCCUPANCY REQUIREMENTS SHALL BE DETERMINED. |
| | 2 COMPLIED. VB- NONSPRINKLERED. . MINIMUM TYPE OF |
| | CONSTRUCTION SHALL BE DETERMINED (SEE TABLE 503). |
| | 3. 2ND REQUEST: LIFE SAFETY PLAN TO SHOW; |
| | OCCUPANCY LOAD GROSS / NET |
| | MEANS OF EGRESS |
| | EXIT ACCESS / EXIT DOORS NOT SHOWN, EXIT LIGHTS NOT |
| | SHOWN |
| | SEATING/ TABLE & CHAIRS |
| | SHELVING UNITS |
| | NOTE SHEET 4 OF 4 PLEASE PROVIDE IN THE EXISTING |
| | DISPLAY ROOM THE LAYOUT OF DISPLAY TABLES, KIOSK OR |
| | RACKS, SHOW THE COMMON PATH OF TRAVEL FOR THIS AREA. |
| | PLEASE SHOW WORST CASE SENARIO, IT APPEARS THE COMMON |
| | PATH OF TRAVEL MAY BE OVER THE ALLOWED 50 FEET. 2010 |
| | FBC-B 1014.3. |
| | |
| | 4. 2ND REQUEST. ACCESSIBILITY REQUIREMENTS WILL NEED TO |
| | BE MET PLEASE REVIEW : 2010 FBC-ACCESSIBILITY CODE |
| | 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF |
| | DISPROPORTIONALITY. |
| | WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH |
| | OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS |
| | DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION, |
| | THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE |
| | EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING |
| | DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE |
| | ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE |
| | ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE |
| | FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN |
| | ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST |
| | ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX |
| | RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE |
| | DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL |
| | ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND |
| | ALARMS. |
| | |
| | PLEASE PROVIDE A WRITTEN DETAILED ACCOUNT WHERE THE 20% |
| | OF THE CONTRACT VALUE ($3,000.00) WILL BE SPENT IN |
| | ACCESSIBLE UPGRADES. FUNDS ARE TO BE SPENT IN THE ORDER |
| | GIVEN IN THE ABOVE CODE REQUIREMENT. NOTE THIS AMOUNT |
| | MAY INCREASE WITH ADDITIONAL WORK REQUIRED FOR CODE |
| | COMPLIANCE. IT WOULD APPEAR THE UPGRADES WOULD NEED TO |
| | TAKE PLACE IN MAKING A SINGLE UNISEX RESTROOM. 2010 |
| | FBC-B 26.4.1.1 PLACES SERVING FOOD OR DRINK ON A |
| | TAKE-OUT, CARRY-OUT OR DELIVERY BASIS ONLY WHICH |
| | PROVIDE NO SEATING SHALL BE REQUIRED TO PROVIDE A |
| | MINIMUM OF ONE BATHROOM ACCESSIBLE TO THE PUBLIC. |
| | |
| | |
| | 5) 426.1 SCOPE. PUBLIC FOOD SERVICE ESTABLISHMENTS OR |
| | FOOD ESTABLISHMENTS SHALL COMPLY WITH DESIGN AND |
| | CONSTRUCTION STANDARDS AS DESCRIBED IN THE FOOD CODE, |
| | CHAPTER 509 PART I OR CHAPTER 500, FLORIDA STATUTES, AS |
| | APPLICABLE. |
| | |
| | NOTE: OTHER ADMINISTRATIVE AND PROGRAMMATIC PROVISIONS |
| | MAY APPLY. SEE DEPARTMENT OF BUSINESS AND PROFESSIONAL |
| | REGULATION (DBPR) RULE 61C-4, FLORIDA ADMINISTRATIVE |
| | CODE CHAPTER 500 AND CHAPTER 509, FLORIDA STATUTES. |
| | |
| | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |