| | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| | REVIEW COMMENTS. |
| | |
| | PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING |
| | COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE |
| | REQUIREMENTS. FBC ENERGY CONSERVATION 505.3 |
| | |
| | PROVIDE VOLTAGE DROP CALCULATION VERIFYING COMPLIANCE |
| | WITH THE ENERGY CODE. FBC-EC 505.7.3 |
| | |
| | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION |
| | FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING |
| | MEANS. NEC 110.22, 110.16, 110.22 |
| | |
| | PROVIDE DIMENSIONS FOR THE DESIGNATED CLEAR WORKING |
| | SPACES REQUIRED AROUND THE ELECTRICAL SERVICE EQUIPMENT |
| | AND PANEL BOARDS. NEC 215.5, 110.26 |
| | |
| | ALL RECEPTACLES LOCATED WITHIN SIX FEET OF A SINKS AND |
| | WITHIN BATHROOMS MUST BE GFCI PROTECTED. NEC 210.8 |
| | |
| | SHOW THE LOCATION OF THE ELECTRICAL SERVICE WITH |
| | DISCONNECT ON A SITE PLAN WITH PROPERTY LINES. VERIFY |
| | THE ELECTRICAL SERVICE MAINS SERVING THIS BUILDING ARE |
| | SIX OR LESS AND GROUPED IN ONE LOCATION. SHOW ALL |
| | METERS, GROUNDING, MAIN DISCONNECTS AND PANEL BOARDS |
| | FOR THE BUILDING SERVICE INCLUDING ALL OTHER EXISTING |
| | OCCUPANCIES REQUIRING ELECTRICAL SERVICE. |
| | NEC 230.2, 230.71, 230.72 |
| | |
| | PROVIDE A MAIN SERVICE DISCONNECT AT A READILY |
| | ACCESSIBLE LOCATION NEAREST THE POINT OF ENTRANCE OF |
| | THE SERVICE CONDUCTORS. NEC 230.70 |
| | |
| | VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS HAS A |
| | FAULT CURRENT RATING THAT IS SUFFICIENT AT NOMINAL |
| | CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| | INTERRUPTED. NEC 110.9 |
| | |
| | PROVIDE A COMPLETE LOAD CALCULATION. PROVIDE A PANEL |
| | SCHEDULE SHOWING ALL LOADS BALANCED. INDICATE THE |
| | PROPOSED WIRING METHOD, WIRE SIZE WITH OVER CURRENT |
| | PROTECTION FOR ALL CIRCUITS. NEC 220.12; 220.14; |
| | 220.12; TABLE 220.12; 230.31 |
| | |
| | VERIFY THE ELECTRICAL SERVICE LOAD IS NOT LESS THAN THE |
| | SUM OF ALL LOADS AS REQUIRED. NEC 215.5; 220.40 |
| | |
| | PROVIDE A SIGN CIRCUIT. NEC 600.5 |
| | |
| | PROVIDE GFCI PROTECTED RECEPTACLE FOR SERVICING THE AIR |
| | CONDITIONING EQUIPMENT. NEC 210.63 |
| | |
| | PROVIDE SHOW WINDOW LIGHTING OUTLETS. NEC 210.62 |
| | |
| | VENDING MACHINES IF PROVIDED SHALL BE PROTECTED WITH |
| | GFCI?S. NEC 422.51 |
| | |
| | PROVIDE A LIGHTING SCHEDULE SHOWING FIXTURE SELECTION |
| | INCLUDING EXIT AND EMERGENCY LIGHTING WITH BATTERY BACK |
| | UP. FBC, ENERGY CONSERVATION 502.3.8; FBC 1011 |
| | |
| | VERIFY THE MEANS OF EGRESS HAS EMERGENCY ILLUMINATION |
| | AND EXIT SIGNS. FBC 1006.2 1011.1 |
| | |
| | |
| | NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR FIRE |
| | ALARM, SECURITY AND DATA SYSTEMS. |
| | |
| | ROBERT LECKY, CBO |
| | ELECTRICAL PLANS REVIEW |
| | |
| | |